3 Mechanical and Electrical Installation NICE7000 User Manual
- 48 -
The following table describes the input and output terminals of HCB-D5.
Table 3-9 Input and output terminals of HCB-D5
Terminal
Name
Function
Terminal Wiring
JP2
Interface for the up call button and indicator
Pins 2 and 3 are for up call input. Pins 1 and 4 are
power supply for the up call indicator (24 VDC output,
load capacity: 40 mA).
1 2 3 4
Up call indicator
Up call
button
JP3
Interface for the down call button and indicator
Pins 2 and 3 are for down call input. Pins 1 and 4
are power supply for the down call indicator (24 VDC
output, load capacity: 40 mA).
1 2 3 4
Down call indicator
Down call
button
JP1
Interface for the fire emergency and elevator lock
switch
Pins 1 and 2 are for elevator lock input. Pins 3 and 4
are for fire emergency input.
1 2 3 4
Fire
emergency
input
Elevator
lock input
S1
Button for setting the floor address.
Hold down the button to adjust the floor address (range
0–56). After you stop pressing, the address number
blinks three times and the setting is successful.
S1
CN1
Modbus communication and power supply terminal.
Pins 2 and 3 are for Modbus communication.
Pins 1 and 4 are for power supply.
1 2 3 4
MOD-
MOD+
24V
COM
Summary of Contents for NICE7000
Page 1: ......
Page 15: ......
Page 16: ...1 Safety Information and Precautions ...
Page 23: ...1 Safety Information and Precautions NICE7000 User Manual 22 ...
Page 24: ...2 Product Information ...
Page 34: ...3 Mechanical and Electrical Installation ...
Page 71: ...4 Use of the Commissioning Tools ...
Page 79: ...5 System Commissioning and Functions ...
Page 102: ...5 System Commissioning and Functions NICE7000 User Manual 100 ...
Page 103: ...6 Function Code Table ...
Page 134: ...6 Function Code Table NICE7000 User Manual 132 ...
Page 135: ...7 Description of Function Codes ...
Page 205: ...8 Troubleshooting ...
Page 224: ...8 Troubleshooting NICE7000 User Manual 222 ...
Page 225: ...9 EMC ...
Page 234: ...9 EMC NICE7000 User Manual 232 ...
Page 237: ......