NICE7000 User Manual 7 Description of Function Codes
- 179 -
Bit
Function
Description
Bit0
Overload
protection
When the motor load or controller load exceeds a certain threshold,
the system performs protection and reports the motor overload or
controller overload fault.
Bit1
Output phase
loss protection
After detecting phase loss on the output side, the system performs
protection and reports the fault.
Bit3
Input phase loss
protection
After detecting phase loss on the input side, the system performs
protection and reports the fault.
Function Code
Parameter Name
Setting Range
Default
Unit
Property
FA-10
Overload protection coefficient
0.50–10.00
1.00
-
★
After detecting that the output current exceeds (FC-10 x Rated motor current) and the
duration lasts the time specified in the inverse time lag curve, the system outputs fault Err11
indicating motor overload.
Function Code
Parameter Name
Setting Range
Default
Unit
Property
FA-11
Overload pre-warning coefficient
50–100
80
%
★
After detecting that the output current exceeds (FA-11 x Rated motor current) and the
duration lasts the time specified in the inverse time lag curve, the system outputs a pre-
warning signal.
Function Code
Parameter Name
Setting Range
Default
Unit
Property
FA-15
Program control selection
0–65535
0
-
★
It is used to select the elevator functions.
Each bit of the function code defines a function, as described in the following table.
If a bit is set to 1, the function indicated by this bit is enabled; if this bit is set to 0, the
function is disabled.
The functions defined by the binary bits are described in the following table.
Bit
Function
Description
Default
Bit0
Super short floor
function
The controller cannot perform shaft auto-tuning if the floor
height is less than 500 mm. After this function is enabled, shaft
auto-tuning can be performed normally.
0
Bit1
Up slow-down
not reset for
super short floor
If this function is enabled, the up slow-down 1 signal does not
reset floor display. The down slow-down 1 signal still resets
floor display. This is valid only when the super short floor
function is enabled.
0
Bit2
Down slow-down
not reset for
super short floor
If this function is enabled, the down slow-down 1 signal does
not reset floor display. The up slow-down 1 signal still resets
floor display. This is valid only when the super short floor
function is enabled.
0
Summary of Contents for NICE7000
Page 1: ......
Page 15: ......
Page 16: ...1 Safety Information and Precautions ...
Page 23: ...1 Safety Information and Precautions NICE7000 User Manual 22 ...
Page 24: ...2 Product Information ...
Page 34: ...3 Mechanical and Electrical Installation ...
Page 71: ...4 Use of the Commissioning Tools ...
Page 79: ...5 System Commissioning and Functions ...
Page 102: ...5 System Commissioning and Functions NICE7000 User Manual 100 ...
Page 103: ...6 Function Code Table ...
Page 134: ...6 Function Code Table NICE7000 User Manual 132 ...
Page 135: ...7 Description of Function Codes ...
Page 205: ...8 Troubleshooting ...
Page 224: ...8 Troubleshooting NICE7000 User Manual 222 ...
Page 225: ...9 EMC ...
Page 234: ...9 EMC NICE7000 User Manual 232 ...
Page 237: ......