FX2N-32DP-IF Profibus-DP Interface Unit
Appendix C:
C-56
C-2-27: FX
2N
-2LC (Motorola Format)
Requirements:
•
Cyclic data is 3 word inputs and 3 word outputs in every cycle. This data is used for
“Simple Communication 3W-IF”. Further information for the simple commnunication 3W-
IF can be found in section 7.2.1 and 7.2.2.
•
Parameter is 70 bytes.
Table C-53: Cyclic Data of FX
2N
-2LC (Intel Format)
Send Data
Receive Data
1st
FROM address
FROM data
2nd
TO data
TO data (read back)
3rd
TO address
TO address (read back)
Table C-54: FX
2N
-2LC (Motorola Format)
Nr.
Parameter Name
Value Setting List
Description
00
(1st)
clear error register
perform nothing
Select error reset command from
the available options. (BFM #10).
reset error register
01
(2nd)
Input Type channel
1 (BFM #70)
Default: 2
Set input type for channel 1.
(BFM #70)
Setting range: 0 to 42
02
(3rd)
Input Type channel
2 (BFM #71)
Default: 2
Select input type for channel 2.
(BFM #71)
Setting range: 0 to 42
03
(4th)
04
(5th)
05
(6th)
06
(7th)
Set Alarm 1 mode
Set Alarm 2 mode
Set Alarm 3 mode
Set Alarm 4 mode
alarm function OFF
•
Select mode of Alarm 1 from the
available options. (BFM #72)
•
Select mode of Alarm 2 from the
available options. (BFM #73)
•
Select mode of Alarm 3 from the
available options. (BFM #74)
•
Select mode of Alarm 4 from the
available options. (BFM #75)
upper limit input value alarm
lower limit input value alarm
upper limit deviation alarm
lower limit deviation alarm
upper/lower limit deviation
range alarm
up. limit in.value alarm + wait
lo. limit in.value alarm + wait
up. limit deviation alarm + wait
lo. limit deviation alarm + wait
upper/lower lim. dev.+ wait
up. limit dev. alarm + re-wait
lo. limit dev. alarm + re-wait
upper/lower lim. dev.+ re-wait
07
(8th)
ALARM1 value for
channel 1.
Default: 0
Set channel 1’s value for Alarm 1.
(BFM #13)
Setting range: -32768 to 32767
Summary of Contents for FX2N-32DP-IF
Page 4: ...FX2N 32DP IF Profibus DP Interface Unit ii...
Page 6: ...FX2N 32DP IF Profibus DP Interface Unit iv...
Page 12: ...FX2N 32DP IF Profibus DP Interface Unit x...
Page 64: ...FX2N 32DP IF Profibus DP Interface Unit Address Setting 6 6 2 MEMO...
Page 78: ...FX2N 32DP IF Profibus DP Interface Unit User Parameter 7 7 14 MEMO...
Page 80: ...FX2N 32DP IF Profibus DP Interface Unit Diagnostic Message 8 8 2 MEMO...
Page 86: ...FX2N 32DP IF Profibus DP Interface Unit Diagnostics 9 9 6 MEMO...
Page 92: ...FX2N 32DP IF Profibus DP Interface Unit Appendix A A 6 Figure A 6 Setting Global Parameter...
Page 96: ...FX2N 32DP IF Profibus DP Interface Unit Appendix A A 10 MEMO...
Page 102: ...FX2N 32DP IF Profibus DP Interface Unit Appendix B B 6 Figure B 6 Setting Global Parameter...
Page 106: ...FX2N 32DP IF Profibus DP Interface Unit Appendix B B 10 MEMO...
Page 192: ...FX2N 32DP IF Profibus DP Interface Unit Appendix C C 86 MEMO...
Page 194: ...FX2N 32DP IF Profibus DP Interface Unit Appendix D D 2 MEMO...
Page 197: ......