Cyclic data is 5 word inputs in every cycle.
•
Parameter is 24 bytes.
Table C-20: Cyclic Data of FX
2N
-4AD-PT Extension Configuration
Send Data
Receive Data
1st
None
Channel 1: present; average value in °C; °F
2nd
Channel 2: present; average value in °C; °F
3rd
Channel 3: present; average value in °C; °F
4th
Channel 4: present; average value in °C; °F
5th
Value of BFM #28 “digital range error latch”
Table C-21: FX
2N
-4AD-PT Extension Configuration
Nr.
Parameter Name
Value Setting List
Description
00
(1st)
channel 1 input
average temperature in 0.1°C
Select input value type for channel 1
from the available options.
(BFM #9, #5, #17, #13)
present temperature in 0.1°C
average temperature in 0.1°F
present temperature in 0.1°F
01
(2th)
channel 2 input
average temperature in 0.1°C
Select input value type for channel 2
from the available options.
(BFM #10, #6, #18, #14)
present temperature in 0.1°C
average temperature in 0.1°F
present temperature in 0.1°F
02
(3th)
channel 3 input
average temperature in 0.1°C
Select input value type for channel 3
from the available options.
(BFM #11, #7, #19, #15)
present temperature in 0.1°C
average temperature in 0.1°F
present temperature in 0.1°F
03
(4th)
channel 4 input
average temperature in 0.1°C
Select input value type for channel 4
from the available options.
(BFM #12, #8, #20, #16)
present temperature in 0.1°C
average temperature in 0.1°F
present temperature in 0.1°F
04
(5th)
data BFM 1 (No. of
samples ch1)
Default: 8
Set the number of samples for
averaged results in channel 1 (BFM
#1).
Setting range: 1 to 4096
05
(6th)
data BFM 2 (No. of
samples ch2)
Default: 8
Set the number of samples for
averaged results in channel 2 (BFM
#2).
Setting range: 1 to 4096
Summary of Contents for FX2N-32DP-IF
Page 4: ...FX2N 32DP IF Profibus DP Interface Unit ii...
Page 6: ...FX2N 32DP IF Profibus DP Interface Unit iv...
Page 12: ...FX2N 32DP IF Profibus DP Interface Unit x...
Page 64: ...FX2N 32DP IF Profibus DP Interface Unit Address Setting 6 6 2 MEMO...
Page 78: ...FX2N 32DP IF Profibus DP Interface Unit User Parameter 7 7 14 MEMO...
Page 80: ...FX2N 32DP IF Profibus DP Interface Unit Diagnostic Message 8 8 2 MEMO...
Page 86: ...FX2N 32DP IF Profibus DP Interface Unit Diagnostics 9 9 6 MEMO...
Page 92: ...FX2N 32DP IF Profibus DP Interface Unit Appendix A A 6 Figure A 6 Setting Global Parameter...
Page 96: ...FX2N 32DP IF Profibus DP Interface Unit Appendix A A 10 MEMO...
Page 102: ...FX2N 32DP IF Profibus DP Interface Unit Appendix B B 6 Figure B 6 Setting Global Parameter...
Page 106: ...FX2N 32DP IF Profibus DP Interface Unit Appendix B B 10 MEMO...
Page 192: ...FX2N 32DP IF Profibus DP Interface Unit Appendix C C 86 MEMO...
Page 194: ...FX2N 32DP IF Profibus DP Interface Unit Appendix D D 2 MEMO...
Page 197: ......