FX2N-32DP-IF Profibus-DP Interface Unit
Appendix C:
C-13
C-2-4:
FX
2N
-4AD Short Configuration (Motorola Format)
Requirements:
•
Cyclic data is 4 word inputs in every cycle.
•
Parameter is 11 bytes.
Table C-10: Cyclic Data of FX
2N
-4AD Short Configuration
(Motorola Format)
Send Data
Receive Data
1st
None
Choose between direct and averaged value ch1
2nd
Choose between direct and averaged value ch2
3rd
Choose between direct and averaged value ch3
4th
Choose between direct and averaged value ch4
Table C-11: FX
2N
-4AD Short Configuration (Motorola Format)
Nr.
Parameter Name
Value Setting List
Description
00
(1st)
Channel 1 input
direct input value ch1
Select input value type for channel 1
from the available options (BFM #9 or
BFM #5).
averaged input value ch1
01
(2nd)
Channel 2 input
direct input value ch2
Select input value type for channel 2
from the available options (BFM #10
or BFM #6).
averaged input value ch2
02
(3rd)
Channel 3 input
direct input value ch3
Select input value type for channel 3
from the available options (BFM #11
or BFM #7).
averaged input value ch3
03
(4th)
Channel 4 input
direct input value ch4
Select input value type for channel 4
from the available options (BFM #12
or BFM #8).
averaged input value ch4
04
(5th)
Next parameter
uses EEPROM.
DON'T write parameter to
EEPROM
The 6th ~9th parameter use
EEPROM. Select “writing to
EEPROM” setting from the available
options.
write parameter to EEPROM
05
*1
(6th)
..channel 3 input
range
preset range -10V to +10V
Select input range for channel 3 from
the available options (BFM #0).
preset range +4mA to +20mA
preset range -20mA to +20mA
channel OFF
06
*1
(7th)
..channel 4 input
range
preset range -10V to +10V
Select input range for channel 4 from
the available options (BFM #0).
preset range +4mA to +20mA
preset range -20mA to +20mA
channel OFF
07
*1
(8th)
..channel 1 input
range
preset range -10V to +10V
Select input range for channel 1 from
the available options (BFM #0).
preset range +4mA to +20mA
preset range -20mA to +20mA
channel OFF
Summary of Contents for FX2N-32DP-IF
Page 4: ...FX2N 32DP IF Profibus DP Interface Unit ii...
Page 6: ...FX2N 32DP IF Profibus DP Interface Unit iv...
Page 12: ...FX2N 32DP IF Profibus DP Interface Unit x...
Page 64: ...FX2N 32DP IF Profibus DP Interface Unit Address Setting 6 6 2 MEMO...
Page 78: ...FX2N 32DP IF Profibus DP Interface Unit User Parameter 7 7 14 MEMO...
Page 80: ...FX2N 32DP IF Profibus DP Interface Unit Diagnostic Message 8 8 2 MEMO...
Page 86: ...FX2N 32DP IF Profibus DP Interface Unit Diagnostics 9 9 6 MEMO...
Page 92: ...FX2N 32DP IF Profibus DP Interface Unit Appendix A A 6 Figure A 6 Setting Global Parameter...
Page 96: ...FX2N 32DP IF Profibus DP Interface Unit Appendix A A 10 MEMO...
Page 102: ...FX2N 32DP IF Profibus DP Interface Unit Appendix B B 6 Figure B 6 Setting Global Parameter...
Page 106: ...FX2N 32DP IF Profibus DP Interface Unit Appendix B B 10 MEMO...
Page 192: ...FX2N 32DP IF Profibus DP Interface Unit Appendix C C 86 MEMO...
Page 194: ...FX2N 32DP IF Profibus DP Interface Unit Appendix D D 2 MEMO...
Page 197: ......