FX2N-32DP-IF Profibus-DP Interface Unit
Appendix C:
C-70
14
(15th)
maximum speed
upper word
Default: 7 (0007 Hex)
Set upper word of maximum speed.
(BFM #1)
Setting range (BFM #1, #0):
-2,147,483,648 to 2,147,483,467
(00000000 to FFFFFFFF Hex)
The range of pulse-converted value
is 1 to 1,000,000 Hz (000000001 to
000F4240 Hex)
15
(16th)
bias speed
Default: 0 (0000 Hex)
Set bias speed. (BFM #2)
Setting range:
0 to 32767 (0000 to 7FFF Hex)
The range of pulse-converted value
is 0 to 30000 Hz (0000 to 7530
Hex)
16
(17th)
Jog speed lower
word
Default: 10000 (2710 Hex)
Set lower word of JOG speed.
(BFM #3)
Setting range (BFM #4, #3):
-2,147,483,648 to 2,147,483,467
(00000000 to FFFFFFFF Hex)
The range of pulse-converted value
is 1 to 1,000,000 Hz (000000001 to
000F4240 Hex)
17
(18th)
Jog speed upper
word
Default: 0 (0000 Hex)
Set lower word of JOG speed.
(BFM #4)
Setting range (BFM #4, #3):
-2,147,483,648 to 2,147,483,467
(00000000 to FFFFFFFF Hex)
The range of pulse-converted value
is 1 to 1,000,000 Hz (000000001 to
000F4240 Hex)
18
(19th)
zero ret. hi. speed
lower word
Default: 41248 (A120 Hex)
Set lower word of the home position
return speed. (BFM #5)
Setting range (BFM #6, #5):
1 to 2,147,483,467 (00000001 to
7FFFFFFF Hex)
The range of pulse-converted value
is 1 to 1,000,000 Hz (000000001 to
000F4240 Hex)
19
(20th)
zero ret. hi. speed
upper word
Default: 7 (0007 Hex)
Set upper word of the home
position return speed. (BFM #6)
Setting range (BFM #6, #5):
1 to 2,147,483,467 (00000001 to
7FFFFFFF Hex)
The range of pulse-converted value
is 1 to 1,000,000 Hz (000000001 to
000F4240 Hex)
Table C-62: FX
2N
-10PG (Motorola Format)
Nr.
Parameter Name
Value Setting List
Description
Summary of Contents for FX2N-32DP-IF
Page 4: ...FX2N 32DP IF Profibus DP Interface Unit ii...
Page 6: ...FX2N 32DP IF Profibus DP Interface Unit iv...
Page 12: ...FX2N 32DP IF Profibus DP Interface Unit x...
Page 64: ...FX2N 32DP IF Profibus DP Interface Unit Address Setting 6 6 2 MEMO...
Page 78: ...FX2N 32DP IF Profibus DP Interface Unit User Parameter 7 7 14 MEMO...
Page 80: ...FX2N 32DP IF Profibus DP Interface Unit Diagnostic Message 8 8 2 MEMO...
Page 86: ...FX2N 32DP IF Profibus DP Interface Unit Diagnostics 9 9 6 MEMO...
Page 92: ...FX2N 32DP IF Profibus DP Interface Unit Appendix A A 6 Figure A 6 Setting Global Parameter...
Page 96: ...FX2N 32DP IF Profibus DP Interface Unit Appendix A A 10 MEMO...
Page 102: ...FX2N 32DP IF Profibus DP Interface Unit Appendix B B 6 Figure B 6 Setting Global Parameter...
Page 106: ...FX2N 32DP IF Profibus DP Interface Unit Appendix B B 10 MEMO...
Page 192: ...FX2N 32DP IF Profibus DP Interface Unit Appendix C C 86 MEMO...
Page 194: ...FX2N 32DP IF Profibus DP Interface Unit Appendix D D 2 MEMO...