FX2N-32DP-IF Profibus-DP Interface Unit
Appendix C:
C-9
*1 To RESET the special function block, set both parameters (6&7) to “reset module”.
While processing a RESET command, no other parameter will be accepted by the
special function block.
As mentioned in the FX
2N
-4AD users guide the EEPROM access takes 300ms. So it is
not possible to RESET the special function block to defaults and set the BFMs 0 to 24 to
a value different to the default value with the same parameter data block.
However, it is possible to send a parameter block to RESET any special function block
that supports the RESET function and afterwards to send a second parameter block to
set the module/s to the desired parameter values.
*2 In this case the default value of the GSD file (high speed) differs from the hardware
default value (normal speed).
*3 The changes of BFM # 0 are written to EEPROM memory. Keep a delay of 300ms
between setting the input range and other write accesses to the EEPROM.
Ex.- changing the gain/offset values
21
(22nd)
..channel 1 (offset/
gain)
no offset/gain setting
Select gain/offset adjust setting for
channel 1 from the available options
(BFM #22).
change offset
change gain
change gain & offset
22
(23rd)
..channel 2 (offset/
gain)
no offset/gain setting
Select gain/offset adjust setting for
channel 2 from the available options
(BFM #22).
change offset
change gain
change gain & offset
23
(24th)
..channel 3 (offset/
gain)
no offset/gain setting
Select gain/offset adjust setting for
channel 2 from the available options
(BFM #22).
change offset
change gain
change gain & offset
24
(25th)
..channel 4 (offset/
gain)
no offset/gain setting
Select gain/offset adjust setting for
channel 2 from the available options
(BFM #22).
change offset
change gain
change gain & offset
Table C-6:
FX
2N
-4AD Extension Configuration (Motorola Format)
Nr.
Parameter Name
Value Setting List
Description
Summary of Contents for FX2N-32DP-IF
Page 4: ...FX2N 32DP IF Profibus DP Interface Unit ii...
Page 6: ...FX2N 32DP IF Profibus DP Interface Unit iv...
Page 12: ...FX2N 32DP IF Profibus DP Interface Unit x...
Page 64: ...FX2N 32DP IF Profibus DP Interface Unit Address Setting 6 6 2 MEMO...
Page 78: ...FX2N 32DP IF Profibus DP Interface Unit User Parameter 7 7 14 MEMO...
Page 80: ...FX2N 32DP IF Profibus DP Interface Unit Diagnostic Message 8 8 2 MEMO...
Page 86: ...FX2N 32DP IF Profibus DP Interface Unit Diagnostics 9 9 6 MEMO...
Page 92: ...FX2N 32DP IF Profibus DP Interface Unit Appendix A A 6 Figure A 6 Setting Global Parameter...
Page 96: ...FX2N 32DP IF Profibus DP Interface Unit Appendix A A 10 MEMO...
Page 102: ...FX2N 32DP IF Profibus DP Interface Unit Appendix B B 6 Figure B 6 Setting Global Parameter...
Page 106: ...FX2N 32DP IF Profibus DP Interface Unit Appendix B B 10 MEMO...
Page 192: ...FX2N 32DP IF Profibus DP Interface Unit Appendix C C 86 MEMO...
Page 194: ...FX2N 32DP IF Profibus DP Interface Unit Appendix D D 2 MEMO...
Page 197: ......