VI
Refrigerant Circuit ]
- 127 -
HWE0913A
GB
Thermis-
tor
TH4
(Discharge)
1) Detects discharge air temper-
ature
2) Provides high-pressure pro-
tection
Degrees Celsius
Resistance
check
0°C[32°F] :698kohm
10°C[50°F] :413kohm
20°C[68°F] :250kohm
30°C[86°F] :160kohm
40°C[104°F] :104kohm
50°C[122°F] : 70kohm
60°C[140°F] : 48kohm
70°C[158°F] : 34kohm
80°C[176°F] : 24kohm
90°C[194°F] :17.5kohm
100°C[212°F] :13.0kohm
110°C[230°F] : 9.8kohm
TH3
(Pipe
temperature)
Controls defrosting during heating
operation
Degrees Celsius
0°C[32°F] :15kohm
10°C[50°F] :9.7kohm
20°C[68°F] :6.4kohm
25°C[77°F] :5.3kohm
30°C[86°F] :4.3kohm
40°C[104°F] :3.1kohm
Resistance
check
TH7
(Outdoor tem-
perature)
1) Detects outdoor air tempera-
ture
2) Controls fan operation
TH5
Fan operated on the 63LS and
TH5 values.
TH6
Controls defrosting during heating
operation
THHS
Inverter
heat sink tem-
perature
Controls inverter cooling fan
based on THHS temperature
Degrees Celsius
0°C[32°F] :161kohm
10°C[50°F] :97kohm
20°C[68°F] :60kohm
25°C[77°F] :48kohm
30°C[86°F] :39kohm
40°C[104°F] :25kohm
THBOX
Control box in-
ternal tempera-
ture detection
Solenoid
valve
SV1a
Discharge-suc-
tion
bypass
1) High/low pressure bypass at
start-up and stopping, and
capacity control during low-
load operation
2) High-pressure-rise preven-
tion
AC208 - 230V
Open while being powered/
closed while not being pow-
ered
Continuity
check with a
tester
SV2
*The SV4c on the P120 and
P144 models closes when
energized and opens when
de-energized.
SV4a - SV4d
Heat
exchanger
capacity control
Controls outdoor unit heat ex-
changer capacity
SV5b
Heat
exchanger
capacity control
Prevents high-pressure-rise
Controls defrost cycle
AC208 - 230V
Closed while being powered/
open while not being powered
SV5c
Allows the refrigerant to pass
through the bypass pipe to pre-
vent an accumulation of liquid re-
frigerant
AC208 - 230V
Open while being powered/
closed while not being pow-
ered
SV9
High-pressure-rise prevention
AC208 - 230V
Open while being powered/
closed while not being pow-
ered
Part
name
Symbols
(functions)
Notes
Usage
Specifications
Check method
R = 7.465k
120
R = 4057
R =
7.465
25/120
t
4057
273 t
1
393
1
exp
R = 15k
0
R = 3460
R = 15
0/80
t
3460
273 t
1
273
1
exp
R = 17k
50
R = 4016
R = 17
25/120
t
4016
273 t
1
323
1
exp
Summary of Contents for PURY-P120TJMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 36: ... II Restrictions 27 HWE0913A GB ...
Page 50: ... II Restrictions 41 41 HWE0913A GB ...
Page 67: ... 58 II Restrictions GB HWE0913A ...
Page 69: ... 60 ...
Page 95: ... 86 III Outdoor Unit Components GB HWE0913A ...
Page 97: ... 88 ...
Page 105: ... 96 IV Remote Controller GB HWE0913A ...
Page 107: ... 98 ...
Page 125: ... 116 ...
Page 145: ... 136 ...
Page 175: ... 166 VII Control GB HWE0913A ...
Page 177: ... 168 ...
Page 203: ... 194 ...
Page 363: ... 354 IX Troubleshooting GB HWE0913A ...
Page 365: ... 356 ...
Page 411: ......