VII
Control ]
- 164 -
HWE0913A
GB
(2) Heating operation
*Note 1. When the outdoor unit goes into the defrost mode, defrost command is sent to the BC controller and indoor units.
Upon reception of the command, the indoor units will go into the defrost mode. When defrosting is completed and
upon receiving the signal that indicates the completion of defrosting, indoor units will resume the heating operation.
*Note 2. Defrost end condition: 10 or more minutes must pass after defrost operation.
or Outdoor unit piping temperature : refer to "-7- Defrost operation control" of [2] Controlling the Outdoor
Unit. (page 147)
Heating operation
Test run mode
ON
Thermostat
ON
Defrost
operation
3-minute restart
prevention
*Note 1,2
*Note 1,2
YES
YES
YES
YES
NO
NO
NO
NO
NO
1. Indoor/outdoor unit fan control
2. Inverter frequency control
3. Indoor unit LEV fully open
4. Solenoid valve control
5. BC controller solenoid valve control
6. BC controller LEV control
Normal operation
Defrost operation
4-way valve ON
During test run mode
1. Indoor unit fan operation at
Very Low speed
2. Inverter output 0Hz
3. Indoor unit LEV fully open
4. Solenoid valve OFF
5. Outdoor unit fan stop
6. BC controller solenoid valve control
7. BC controller LEV control
Stopping the
defrost operation
1. Indoor unit fan stop
2. Inverter defrost frequency control
3. Indoor unit LEV fully open
4. Solenoid valve control
5. Outdoor unit fan stop
6. BC controller solenoid valve control
7. BC controller LEV control
4-way valve OFF
1
3
Stopping the defrost operation
Unit in the stopped state
Summary of Contents for PURY-P120TJMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 36: ... II Restrictions 27 HWE0913A GB ...
Page 50: ... II Restrictions 41 41 HWE0913A GB ...
Page 67: ... 58 II Restrictions GB HWE0913A ...
Page 69: ... 60 ...
Page 95: ... 86 III Outdoor Unit Components GB HWE0913A ...
Page 97: ... 88 ...
Page 105: ... 96 IV Remote Controller GB HWE0913A ...
Page 107: ... 98 ...
Page 125: ... 116 ...
Page 145: ... 136 ...
Page 175: ... 166 VII Control GB HWE0913A ...
Page 177: ... 168 ...
Page 203: ... 194 ...
Page 363: ... 354 IX Troubleshooting GB HWE0913A ...
Page 365: ... 356 ...
Page 411: ......