-9- Capacity Control of Outdoor Fan and Heat Exchanger
(1) Control method
Depending on the capacity required, the rotation speed of the outdoor unit fan is controlled by the inverter to keep a constant
condensing temperature of (outside tempe10°C [50°F]) during cooling operation and a constant evaporation temper-
ature of (0°C [32°F] =0.71 <Pa [103psi]) during heating operation.
The OS in the multiple-outdoor-unit system operates at the actual outdoor unit fan control value that is calculated by the OS
based on the preliminary outdoor unit fan control value that the OC determines.
(2) Control
Outdoor unit fan stops while the compressor is stopped (except in the presence of input from snow sensor).
The fan operates at full speed for 5 seconds after start-up.(Only when TH7<0°C [32°F])
The outdoor unit fan stops during defrost operation.
On the P120 and P144 models of outdoor units, before the second fan goes into operation, the capacity of the first fan is
reduced to 50%.
(3) Outdoor unit heat exchanger capacity control patterns
SV4c turns on when energized on the P96 model, and it turns on when de-energized on the P120 and P144 models.
(All other valves turn on when energized.)
Model Operation
mode
Operation
patterns
Solenoid valve
SV4a
SV4b
SV4c
SV4d
SV5c
P72 model
Cooling-only
Cooling-main
1
OFF
OFF
-
ON
ON
2
OFF
OFF
-
OFF
ON
3
OFF
ON
-
OFF
ON
4
ON
OFF
-
OFF
ON
5
ON
ON
-
OFF
OFF
Heating-only
1
ON
ON
-
OFF
OFF
Heating-main
1
ON
ON
-
ON
OFF
2
ON
ON
-
OFF
OFF
Defrost
1
ON
ON
-
OFF
OFF
P96 model
Cooling-only
Cooling-main
1
OFF
OFF
OFF
ON
ON
2
OFF
OFF
OFF
OFF
ON
3
OFF
OFF
ON
OFF
ON
4
OFF
ON
ON
OFF
ON
5
ON
ON
ON
OFF
OFF
Heating-only
1
ON
ON
ON
OFF
OFF
Heating-main
1
ON
ON
ON
ON
OFF
2
ON
ON
ON
OFF
OFF
Defrost
1
ON
ON
ON
OFF
OFF
P120, P144 models
Cooling-only
Cooling-main
1
OFF
OFF
OFF
ON
ON
2
OFF
OFF
OFF
OFF
ON
3
OFF
ON
OFF
OFF
ON
4
ON
ON
OFF
OFF
ON
5
ON
ON
ON
OFF
OFF
Heating-only
1
ON
ON
ON
OFF
OFF
Heating-main
1
ON
ON
ON
ON
OFF
2
ON
ON
ON
OFF
OFF
Defrost
1
ON
ON
ON
OFF
ON
Summary of Contents for PURY-P120TJMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 36: ... II Restrictions 27 HWE0913A GB ...
Page 50: ... II Restrictions 41 41 HWE0913A GB ...
Page 67: ... 58 II Restrictions GB HWE0913A ...
Page 69: ... 60 ...
Page 95: ... 86 III Outdoor Unit Components GB HWE0913A ...
Page 97: ... 88 ...
Page 105: ... 96 IV Remote Controller GB HWE0913A ...
Page 107: ... 98 ...
Page 125: ... 116 ...
Page 145: ... 136 ...
Page 175: ... 166 VII Control GB HWE0913A ...
Page 177: ... 168 ...
Page 203: ... 194 ...
Page 363: ... 354 IX Troubleshooting GB HWE0913A ...
Page 365: ... 356 ...
Page 411: ......