IX
Troubleshooting ]
- 308 -
HWE0913A
GB
Check whether the BC board output signal corresponds with the solenoid valve operation correspond.
1) SVA, SVB, SVC
SVA, SVB, and SVC turn on or off according to the indoor unit operation mode.
SVM1 and SVM2
SVM1 and SVM2 turn on or off according to the indoor unit operation mode.
2) SVA, SVB, SVC
Measure the temperature at the upstream and downstream pipes
and
of SVA.
Measure the temperature at the upstream and downstream
pipes and
of SVB.
Mode
Cooling
Heating
Stopped
Defrost
Fan
Port
SVA
ON
OFF
OFF
OFF
OFF
SVB
OFF
ON
OFF
OFF
OFF
SVC
ON
OFF
OFF
OFF
ON
Operation
mode
Cooling only
Cooling main
Heating only
Heating main
Defrost
Stopped
SVM1
ON
Pressure dif-
ferential con-
trol OFF or
ON
OFF
OFF
ON
OFF
SVM2
OFF
OFF
Pressure dif-
ferential con-
trol OFF or
ON
Pressure dif-
ferential con-
trol OFF or
ON
OFF
OFF
Summary of Contents for PURY-P120TJMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 36: ... II Restrictions 27 HWE0913A GB ...
Page 50: ... II Restrictions 41 41 HWE0913A GB ...
Page 67: ... 58 II Restrictions GB HWE0913A ...
Page 69: ... 60 ...
Page 95: ... 86 III Outdoor Unit Components GB HWE0913A ...
Page 97: ... 88 ...
Page 105: ... 96 IV Remote Controller GB HWE0913A ...
Page 107: ... 98 ...
Page 125: ... 116 ...
Page 145: ... 136 ...
Page 175: ... 166 VII Control GB HWE0913A ...
Page 177: ... 168 ...
Page 203: ... 194 ...
Page 363: ... 354 IX Troubleshooting GB HWE0913A ...
Page 365: ... 356 ...
Page 411: ......