VIII
Test Run Mode ]
- 182 -
HWE0913A
GB
Operation
Outdoor unit model
PURY-P192TSJMU-A
PURY-P96TJMU-A
PURY-P96TJMU-A
Model name of BC controller
CMB-P108NU-GA
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
26.7°C/19.4°C [80 °F/67 °F]
Outdoor
35°C/ [95 °F/]
Indoor unit
No. of connected units
Unit
6
No. of units in operation
6
Model
-
30/30/30/30/36/36
Piping
Main pipe
m
[ft]
5 [16-3/8"]
Branch pipe
10 [32-3/4"]
Total pipe length
65 [213-1/4"]
Fan speed
-
Hi
Amount of refrigerant
kg
[lbs-oz]
42.4 [93]
Outdoor
unit
Electric current
A
44.8
Voltage
V
230
Compressor frequency
Hz
61
61
LEV open-
ing
Indoor unit
Pulse
230/230/230/230/275/275
BC controller (1/2/3)
2000/2000/270
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
2.78/0.90
[403/131]
2.78/0.90
[403/131]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.70/2.70
[392/392]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
87 [189]
87 [189]
Heat exchanger outlet
(TH3)
41 [106]
41 [106]
Accumulator inlet
8 [46]
8 [46]
Accumulator outlet
8 [46]
8 [46]
Compressor inlet
19 [66]
19 [66]
Compressor shell bottom
42 [108]
40 [104]
Indoor unit
LEV inlet
19 [66]
Heat exchanger inlet
6 [43]
Summary of Contents for PURY-P120TJMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 36: ... II Restrictions 27 HWE0913A GB ...
Page 50: ... II Restrictions 41 41 HWE0913A GB ...
Page 67: ... 58 II Restrictions GB HWE0913A ...
Page 69: ... 60 ...
Page 95: ... 86 III Outdoor Unit Components GB HWE0913A ...
Page 97: ... 88 ...
Page 105: ... 96 IV Remote Controller GB HWE0913A ...
Page 107: ... 98 ...
Page 125: ... 116 ...
Page 145: ... 136 ...
Page 175: ... 166 VII Control GB HWE0913A ...
Page 177: ... 168 ...
Page 203: ... 194 ...
Page 363: ... 354 IX Troubleshooting GB HWE0913A ...
Page 365: ... 356 ...
Page 411: ......