II
Restrictions ]
- 53 -
HWE0913A
GB
1. Refrigerant
pipe
size
(1) Between outdoor unit and the first twinning pipe (Part A)
(2) Between BC controller and indoor unit (Sections a, b, c, d, e, and f )
(3) Between the main and sub BC controllers (Section C)
Select the proper size pipes for the main unit based on the total capacity of the indoor units that are connected to both sub
BC controllers. Select the proper size pipes for the sub controller side based on the total capacity of the indoor units that are
connected to the sub controller.
Unit : mm [inch]
Outdoor units
Refrigerant pipe size
Connection to outdoor unit and BC controller
Low-pressure pipe
High-pressure pipe
Low-pressure pipe
High-pressure pipe
72
ø19.05 [3/4"]
ø15.88 [5/8"]
ø19.05 [3/4"]
ø15.88 [5/8"]
96
ø22.2 [7/8"]
ø19.05 [3/4"]
ø22.2 [7/8"]
ø19.05 [3/4"]
120
ø28.58 [1-1/8"]
ø28.58 [1-1/8"]
144
ø22.2[7/8"]
ø22.2 [7/8"]
168
192
216
ø28.58 [1-1/8"]
ø28.58 [1-1/8"]
240
ø34.93 [1-3/8"]
264
ø34.93 [1-3/8"]
288
Unit : mm [inch]
Indoor unit
Refrigerant pipe size
Indoor unit connection
(Flare connection for all models)
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
P06, P08, P12, P15, P18
ø6.35 [1/4"]
ø12.7 [1/2"]
ø6.35 [1/4"]
ø12.7 [1/2"]
P24, P27, P30
ø9.52 [3/8"]
ø15.88 [5/8"]
ø9.52 [3/8"]
ø15.88 [5/8"]
P36, P48, P54
P72
ø12.7 [1/2"]
ø19.05 [3/4"]
ø12.7 [1/2"]
ø19.05 [3/4"]
P96
ø22.2
[7/8"]
ø22.2
[7/8"]
Unit : mm [inch]
Indoor unit
Refrigerant pipe size (Brazed connection on all models )
Liquid pipe
High-pressure gas pipe
Low-pressure gas pipe
- P72
ø9.52 [3/8"]
ø15.88 [5/8"]
ø19.05 [3/4"]
P73 - P108
ø19.05 [3/4"]
ø22.2 [7/8"]
P109 - P126
ø12.7 [1/2"]
ø28.58 [1-1/8"]
P127 - P144
ø22.2 [7/8"]
P145 - P168
ø15.88 [5/8"]
Summary of Contents for PURY-P120TJMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 36: ... II Restrictions 27 HWE0913A GB ...
Page 50: ... II Restrictions 41 41 HWE0913A GB ...
Page 67: ... 58 II Restrictions GB HWE0913A ...
Page 69: ... 60 ...
Page 95: ... 86 III Outdoor Unit Components GB HWE0913A ...
Page 97: ... 88 ...
Page 105: ... 96 IV Remote Controller GB HWE0913A ...
Page 107: ... 98 ...
Page 125: ... 116 ...
Page 145: ... 136 ...
Page 175: ... 166 VII Control GB HWE0913A ...
Page 177: ... 168 ...
Page 203: ... 194 ...
Page 363: ... 354 IX Troubleshooting GB HWE0913A ...
Page 365: ... 356 ...
Page 411: ......