IX
Troubleshooting ]
- 215 -
HWE0913A
GB
1. Error
Code
Indoor unit fan operation error
2. Error definition and error detection method
1) During operation, it has been continuously detected for 100 seconds that the auxiliary relay (X13) for fan fault detection is not
excited.
3. Cause, check method and remedy
4109
Cause
Check method and remedy
(1)
Auxiliary relay (X13) fault
Coil failure, disconnected coil
(2)
Connector (CN28) is disconnected.
Check the connector for proper connection.
(3)
Blown fuse
Check the fuse on the control circuit board.
(4)
Motor error (thermistor error inside the motor)
Check the unit fan for proper operation in the test run
mode.
If no problems are found with items 1 through 3 above and
the fan does not operate, replace the motor.