HWE0913A
GB
4. Thickness and refrigerant type indicated on the piping materials
Ask the pipe manufacturer for the symbols indicated on the piping material for new refrigerant.
5. Flare processing (O-material (Annealed) and OL-material only)
The flare processing dimensions for the pipes that are used in the R410A system are larger than those in the R22 system.
(ø19.05 pipes should have a radial thickness of 1.2 t and be made of annealed materials.)
If a clutch-type flare tool is used to flare the pipes in the system using R410A, the length of the pipes must be between 1.0
and 1.5 mm. For margin adjustment, a copper pipe gauge is necessary.
6. Flare
nut
The flare nut type has been changed to increase the strength. The size of some of the flare nuts have also been changed.
The figures in the radial thickness column are based on the Japanese standards and provided only as a reference. Use pipes
that meet the local standards.
Flare processing dimensions (mm[in.])
Pipe size (mm[in.])
A dimension (mm)
R410A
R22, R407C
ø6.35
[1/4"]
9.1
9.0
ø9.52
[3/8"]
13.2
13.0
ø12.7
[1/2"]
16.6
16.2
ø15.88
[5/8"]
19.7
19.4
ø19.05
[3/4"]
24.0
23.3
Flare nut dimensions (mm[in.])
Pipe size (mm[in.])
B dimension (mm)
R410A
R22, R407C
ø6.35
[1/4"]
17.0
17.0
ø9.52
[3/8"]
22.0
22.0
ø12.7
[1/2"]
26.0
24.0
ø15.88
[5/8"]
29.0
27.0
ø19.05
[3/4"]
36.0
36.0
Dimension A
Dimension B
Summary of Contents for PURY-P120TJMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 36: ... II Restrictions 27 HWE0913A GB ...
Page 50: ... II Restrictions 41 41 HWE0913A GB ...
Page 67: ... 58 II Restrictions GB HWE0913A ...
Page 69: ... 60 ...
Page 95: ... 86 III Outdoor Unit Components GB HWE0913A ...
Page 97: ... 88 ...
Page 105: ... 96 IV Remote Controller GB HWE0913A ...
Page 107: ... 98 ...
Page 125: ... 116 ...
Page 145: ... 136 ...
Page 175: ... 166 VII Control GB HWE0913A ...
Page 177: ... 168 ...
Page 203: ... 194 ...
Page 363: ... 354 IX Troubleshooting GB HWE0913A ...
Page 365: ... 356 ...
Page 411: ......