IX
Troubleshooting ]
- 242 -
HWE0913A
GB
1. Error
Code
Open-circuited IPM/Loose ACCT connector (Detail code 119)
2. Error definition and error detection method
Presence of enough current cannot be detected during the self-diagnostic operation immediately before inverter startup.
3. Cause, check method and remedy
Refer to section -7- "Inverter (YJMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the
inverter.(page 320)
1. Error
Code
Faulty ACCT wiring (Detail code 120)
2. Error definition and error detection method
Presence of target current cannot be detected during the self-diagnostic operation immediately before startup. (Detection of
improperly mounted ACCT sensor)
3. Cause, check method and remedy
P72 model
P96, P120, P144 models
Refer to section -7- "Inverter (TJMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the
inverter.(page 310)
5301
(YJMU-A)
Cause
Check method and remedy
(1)
Inverter output wiring problem
Check output wiring connections.
Confirm that the U- and W-phase output cables are put through CT12
and CT22 on the INV board respectively.
(2)
Inverter failure
Refer to IX [4] -7- (2) [3], [4].(page 322)
(3)
Compressor failure
Refer to IX [4] -7- (2) [2].(page 322)
5301
(TJMU-A)
Cause
Check method and remedy
(1)
Inverter output wiring problem
Check output wiring connections.
Confirm that the U- and W-phase output cables are put through CT12
and CT22 on the INV board respectively.
(2)
Inverter failure
Refer to IX [4] -7- (2) [3], [4].(page 313)
(3)
Compressor failure
Refer to IX [4] -7- (2) [2].(page 312)
(4)
INV board failure
Replace the INV board.
Cause
Check method and remedy
(1)
Wrongly mounted ACCT sensor
Check for proper mounting of ACCT.
Refer to IX [4] -7- (4).
(2)
ACCT sensor failure
Refer to IX [4] -7- (4).(page 316)
(3)
Inverter failure
Refer to IX [4] -7- (2) [3], [4].(page 313)
(4)
Compressor failure
Refer to IX [4] -7- (2) [2].(page 312)
Summary of Contents for PURY-P120TJMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 36: ... II Restrictions 27 HWE0913A GB ...
Page 50: ... II Restrictions 41 41 HWE0913A GB ...
Page 67: ... 58 II Restrictions GB HWE0913A ...
Page 69: ... 60 ...
Page 95: ... 86 III Outdoor Unit Components GB HWE0913A ...
Page 97: ... 88 ...
Page 105: ... 96 IV Remote Controller GB HWE0913A ...
Page 107: ... 98 ...
Page 125: ... 116 ...
Page 145: ... 136 ...
Page 175: ... 166 VII Control GB HWE0913A ...
Page 177: ... 168 ...
Page 203: ... 194 ...
Page 363: ... 354 IX Troubleshooting GB HWE0913A ...
Page 365: ... 356 ...
Page 411: ......