IX
Troubleshooting ]
- 265 -
HWE0913A
GB
1. Error
Code
Wrong number of connected units
2. Error definition and error detection method
The number of connected indoor units is "0" or exceeds the allowable value.
3. Error source, cause, check method and remedy
7102
Error source
Cause
Check method and remedy
Outdoor unit
(1)
Number of indoor units connected to the outdoor
terminal block (TB3) for indoor/ outdoor transmis-
sion lines exceeds limitations described below.
1)
Check whether the number of units con-
nected to the outdoor terminal block
(TB3) for indoor/ outdoor transmission
lines does not exceed the limitation. (See
(1) and (2) on the left.)
2)
Check (2) - (3) on the left.
3)
Check whether the transmission line for
the terminal block for centralized control
(TB7) is not connected to the terminal
block for the indoor/outdoor transmission
line (TB3).
4)
Check the setting for the model selection
switch on the outdoor unit (Dipswitches
SW5-7 on the outdoor unit control board).
(2)
Disconnected transmission line from the outdoor
unit or BC controller
(3)
Short-circuited transmission line
When (2) and (3) apply, the following display will
appear.
ME remote controller
Nothing appears on the remote controller be-
cause it is not powered.
MA remote controller
"HO" or "PLEASE WAIT" blinks.
(4)
The model selection switch (SW5-7) on the out-
door unit is set to OFF. (Normally set to ON)
(5)
Outdoor unit address setting error
The outdoor units in the same refrigerant circuit do
not have sequential address numbers.
(6)
A BC controller other than the GA or HA type is
connected to a system that consists of P168 or
larger models of units OR a BC controller other
than the HA type is used as the main controller in
a system that consists of P264 or larger models of
units.
Restriction on the number of units
Number of units
0 or 1
0 or 1
1
(P72- P144 models only)
0,1 or 2
1 - 18 : P72 model
1 - 24 : P96 model
1 - 30 : P120 model
1 - 36 : P144 model
1 - 42 : P168 model
1 - 48 : P192 model
2 - 50 : P216 model
2 - 50 : P240 model
2 - 50 : P264 model
2 - 50 : P288 model
1 : P72 - P144 models
2 : P168 - P288 models
Total number of indoor units
Total number of LOSSNAY
units (During auto address
start-up only)
Number of Sub BC controllers
Number of
Main BC controllers
Number of BC controllers
Total number of outdoor units
Summary of Contents for PURY-P120TJMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 36: ... II Restrictions 27 HWE0913A GB ...
Page 50: ... II Restrictions 41 41 HWE0913A GB ...
Page 67: ... 58 II Restrictions GB HWE0913A ...
Page 69: ... 60 ...
Page 95: ... 86 III Outdoor Unit Components GB HWE0913A ...
Page 97: ... 88 ...
Page 105: ... 96 IV Remote Controller GB HWE0913A ...
Page 107: ... 98 ...
Page 125: ... 116 ...
Page 145: ... 136 ...
Page 175: ... 166 VII Control GB HWE0913A ...
Page 177: ... 168 ...
Page 203: ... 194 ...
Page 363: ... 354 IX Troubleshooting GB HWE0913A ...
Page 365: ... 356 ...
Page 411: ......