-10- Control at Initial Start-up
When started up for the first time before 12 hours have elapsed after power on, the unit goes into the initial startup mode.
At the completion of the initial operation mode on the OC and OS, they will go into the normal control mode.
1. Flowchart of initial operation
(1) P72, P96, P120, P144 models
50 F 60Hz
or F < 50Hz
Initial startup mode starts.
Completed in the integrated operation time of 35 minutes.
Initial startup mode complete
or the discharge superheat (TH4 - Tc) is detected (within
5 minutes of startup) that remains above approximately
20 degrees for one minute .
Completed in the integrated operation time of 90 minutes.