IX
Troubleshooting ]
- 228 -
HWE0913A
GB
1. Error
Code
IPM error (Detail code 101)
2. Error definition and error detection method
In the case of 4250
P72 model
Overcurrent is detected by the overcurrent detection resistor (RSH) on the INVboard.
P96, P120, P144 models
IPM error signal is detected.
In the case of 4255
IPM error signal is detected.
3. Cause, check method and remedy
In the case of 4250
P72 model
P96, P120, P144 models
In the case of 4255
Refer to section -7- "Inverter (TJMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the
inverter.(page 310)
4250
4255
(TJMU-A)
Cause
Check method and remedy
(1)
Inverter output related
Refer to IX [4] -7- (2) [1] - [4].(page 312)
Cause
Check method and remedy
(1)
Inverter output related
Refer to IX [4] -7- (2) [1] - [4].(page 312)
(2)
Same as 4230 error
Same as 4230 error
Cause
Check method and remedy
(1)
Fan motor abnormality
Refer to IX [4] -7- (2) [5].(page 314)
(2)
Fan board failure
Refer to IX [4] -7- (2) [6].(page 314)
(3)
Electromagnetic contactor (52F)
actuation failure (P120, P144 on-
ly)
Check the wiring between the FAN board, 52F, and fan motor.
(page 295)
Summary of Contents for PURY-P120TJMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 36: ... II Restrictions 27 HWE0913A GB ...
Page 50: ... II Restrictions 41 41 HWE0913A GB ...
Page 67: ... 58 II Restrictions GB HWE0913A ...
Page 69: ... 60 ...
Page 95: ... 86 III Outdoor Unit Components GB HWE0913A ...
Page 97: ... 88 ...
Page 105: ... 96 IV Remote Controller GB HWE0913A ...
Page 107: ... 98 ...
Page 125: ... 116 ...
Page 145: ... 136 ...
Page 175: ... 166 VII Control GB HWE0913A ...
Page 177: ... 168 ...
Page 203: ... 194 ...
Page 363: ... 354 IX Troubleshooting GB HWE0913A ...
Page 365: ... 356 ...
Page 411: ......