IX
Troubleshooting ]
- 336 -
HWE0913A
GB
Compressor cover
(top)
4. Remove the compressor cover (top).
5. Remove the compressor wires, compressor covers
(right and left), and belt heater.
Protection for the
sealing material
Suction piping
Protection for the
compressor cover
6. Place protective materials on the insulation lining of
the compressor cover and on the sealing material
on the compressor suction pipe to protect them from
the torch flame, debraze the pipe, and replace the
compressor.
Belt heater
Compressor covers
(right and left)
(The inside of the compressor
cover is lined with sound
insulation material.)