VIII
Test Run Mode ]
- 188 -
HWE0913A
GB
Operation
Outdoor unit model
PURY-P192TSJMU-A
PURY-P96TJMU-A
PURY-P96TJMU-A
Model name of BC controller
CMB-P108NU-GA
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
21.1°C/ [70 °F/]
Outdoor
8.3°C/6.1°C [47°F/43°F]
Indoor unit
No. of connected units
Unit
6
No. of units in operation
6
Model
-
30/30/30/30/36/36
Piping
Main pipe
m
[ft]
5 [16-3/18"]
Branch pipe
10 [32-3/4"]
Total pipe length
65 [213-1/4"]
Fan speed
-
Hi
Amount of refrigerant
kg
[lbs-oz]
42.4 [93]
Outdoor
unit
Electric current
A
49.7
Voltage
V
230
Compressor frequency
Hz
74
74
LEV open-
ing
Indoor unit
Pulse
295/295/295/295/350/350
BC controller (1/2/3)
110/110/1050
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
2.52/0.63
[365/91]
2.52/0.63
[365/91]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.48/2.27
[360/329]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
78 [172]
78 [172]
Heat exchanger outlet
(TH6)
0 [32]
0 [32]
Accumulator inlet
-2 [28]
-2 [28]
Accumulator outlet
-3 [27]
-3 [27]
Compressor inlet
-3 [27]
-3 [27]
Compressor shell bottom
40 [104]
40 [104]
Indoor unit
LEV inlet
36 [97]
Heat exchanger inlet
68 [154]
Summary of Contents for PURY-P120TJMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 36: ... II Restrictions 27 HWE0913A GB ...
Page 50: ... II Restrictions 41 41 HWE0913A GB ...
Page 67: ... 58 II Restrictions GB HWE0913A ...
Page 69: ... 60 ...
Page 95: ... 86 III Outdoor Unit Components GB HWE0913A ...
Page 97: ... 88 ...
Page 105: ... 96 IV Remote Controller GB HWE0913A ...
Page 107: ... 98 ...
Page 125: ... 116 ...
Page 145: ... 136 ...
Page 175: ... 166 VII Control GB HWE0913A ...
Page 177: ... 168 ...
Page 203: ... 194 ...
Page 363: ... 354 IX Troubleshooting GB HWE0913A ...
Page 365: ... 356 ...
Page 411: ......