IX
Troubleshooting ]
- 244 -
HWE0913A
GB
1. Error
Code
Temperature sensor fault
2. Error definition and error detection method
A short-circuit or an open-circuit of the humidity sensor is detected during operation.
3. Cause, check method and remedy
5401
Cause
Check method and remedy
(1)
Connector contact failure (CN30) (Loose con-
nector)
1)
Check the connector for proper contact.
Reconnect the connector, and operate the unit to check for
proper operation.
(2)
Broken or partially broken humidity sensor wire 2)
Check for broken humidity sensor wire.
(3)
Humidity sensor fault
3)
Check the output voltage across No. 1 and No. 3 pins of
connector CN30 with the connector being connected to the
indoor unit control board.
30% : 1.25V
40% : 1.52V
50% : 1.88V
60% : 2.19V
70% : 2.48V
80% : 2.79V
(4)
Indoor unit control board (detection circuit) fault 4)
If the above items check out okay, replace the indoor unit
control board.
Summary of Contents for PURY-P120TJMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 36: ... II Restrictions 27 HWE0913A GB ...
Page 50: ... II Restrictions 41 41 HWE0913A GB ...
Page 67: ... 58 II Restrictions GB HWE0913A ...
Page 69: ... 60 ...
Page 95: ... 86 III Outdoor Unit Components GB HWE0913A ...
Page 97: ... 88 ...
Page 105: ... 96 IV Remote Controller GB HWE0913A ...
Page 107: ... 98 ...
Page 125: ... 116 ...
Page 145: ... 136 ...
Page 175: ... 166 VII Control GB HWE0913A ...
Page 177: ... 168 ...
Page 203: ... 194 ...
Page 363: ... 354 IX Troubleshooting GB HWE0913A ...
Page 365: ... 356 ...
Page 411: ......