IX
Troubleshooting ]
- 312 -
HWE0913A
GB
(2) Inverter output related troubles
Items to be checked
Phenomena
Remedy
[1]
Check the INV
board error
detection cir-
cuit.
<P72 model>
1)
IPM/overcurrent breaker trip
(4250 Detail code No. 101, 104,
105, 106, and 107)
Replace the INV board.
(1)
Disconnect the invert-
er output wire from
the terminals of the
INV board (SC-U,
SC-V, SC-W).
2)
Logic error
(4220 Detail code No. 111)
Replace the INV board.
(2)
Put the outdoor unit
into operation.
3)
ACCT sensor circuit failure
(5301 Detail code No.117)
Replace the INV board.
4)
IPM open
(5301 Detail code No.119)
Normal
<P96, P120, P144 mod-
els>
1)
IPM/overcurrent breaker trip
(4250 Detail code No. 101, 103,
104, 105, 106, and 107)
See the section "Troubleshooting
the IPM" ( Refer to - 7 - (5) ).
Replace the IPM, and put the out-
door unit back into operation.
If the problem persists, replace the
INV board.
(1)
Disconnect the invert-
er output wire from
the output terminals
(U, V, W) of the IPM.
2)
Logic error
(4220 Detail code No. 111)
See the section "Troubleshooting
the IPM" ( Refer to - 7 - (5) ).
Replace the IPM, and put the out-
door unit back into operation.
If the problem persists, replace the
INV board.
Replace the INV board, and put
the outdoor unit back into opera-
tion.
If the problem persists, replace the
DCCT.
(2)
Put the outdoor unit
into operation.
3)
ACCT sensor circuit failure
(5301 Detail code No.117)
Replace the INV board.
4)
DCCT sensor circuit failure
(5301 Detail code No.118)
Replace the DCCT board.
Replace the DCCT, and put the
outdoor unit back into operation.
If the problem persists, replace the
INV board.
5)
IPM open
(5301 Detail code No.119)
Normal
[2]
Check for
compressor
ground fault or
coil error.
Disconnect the compres-
sor wiring, and check the
compressor Meg, and coil
resistance.
1)
Compressor Meg failure
Error if less than 1 Mohm.
When no liquid refrigerant in the
compressor
Replace the compressor
Check that no liquid refrigerant in
the compressor.
2)
Compressor coil resistance failure
Coil resistance value of 0.20 ohm
(20°C [68°F]) : P72 model
Coil resistance value of 0.09 ohm
(20°C [68°F]) :P96 - P144 models
[TJMU-A]
Summary of Contents for PURY-P120TJMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 36: ... II Restrictions 27 HWE0913A GB ...
Page 50: ... II Restrictions 41 41 HWE0913A GB ...
Page 67: ... 58 II Restrictions GB HWE0913A ...
Page 69: ... 60 ...
Page 95: ... 86 III Outdoor Unit Components GB HWE0913A ...
Page 97: ... 88 ...
Page 105: ... 96 IV Remote Controller GB HWE0913A ...
Page 107: ... 98 ...
Page 125: ... 116 ...
Page 145: ... 136 ...
Page 175: ... 166 VII Control GB HWE0913A ...
Page 177: ... 168 ...
Page 203: ... 194 ...
Page 363: ... 354 IX Troubleshooting GB HWE0913A ...
Page 365: ... 356 ...
Page 411: ......