
[
IX
Troubleshooting ]
- 339 -
HWE0913A
GB
(2) Check valve (CV4a, CV6a, CV8a, CV9a, CV10a) replacement procedures
①
Remove the Solenoid valve block ASSY following
"(1) Solenoid valve block ASSY (SV4a, SV4b, SV4d) replacement
procedures"
on the front page.
②
Debraze H-M parts (total 6 places), and remove the Check valve ASSY.
③
Replace the Check valve (CV4a, CV6a, CV8a, CV9a, CV10a) to be serviced while it is removed from the unit.
Braze the pipes as they were according to the angle of the pipes on the next page (Figure as viewed from point Q).
④
Mount the solenoid valve block ASSY, coil cover, and peripheral cables back in place according to
"(1) Solenoid valve
block ASSY (SV4a, SV4b, SV4d) replacement procedures"
on the front page.
②③
H
(
φ
19.05 [3/4"])
②③
I
(
φ
15.88 [5/8"])
Heat exchanger
②③
J
(
φ
12.7 [1/2"])
②③
K
(
φ
6.35 [1/4"])
* After removing Solenoid valve block ASSY
Part A (Refer to the next page.)
*
Precautions for replacing Check valve
•
Be sure to perform no-oxidation brazing when brazing.
•
Place a wet towel on the check valve when heating pipes to keep the temperature of the valve from exceed-
ing 120°C [248°F].
•
After brazing, check the condition around the brazing. After confirming no leakage, evacuate the air
inside. (*1)
•
Perform carefully with the flame direction so that it does not burn cables and plates etc. in the unit.
•
Remove the brazing part protecting heat exchanger fins not to be burn, and replace the service parts.
*1: Refer to Chapter I [8] Vacuum Drying (Evacuation) for detailed procedure.
Summary of Contents for PURY-P120TJMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 36: ... II Restrictions 27 HWE0913A GB ...
Page 50: ... II Restrictions 41 41 HWE0913A GB ...
Page 67: ... 58 II Restrictions GB HWE0913A ...
Page 69: ... 60 ...
Page 95: ... 86 III Outdoor Unit Components GB HWE0913A ...
Page 97: ... 88 ...
Page 105: ... 96 IV Remote Controller GB HWE0913A ...
Page 107: ... 98 ...
Page 125: ... 116 ...
Page 145: ... 136 ...
Page 175: ... 166 VII Control GB HWE0913A ...
Page 177: ... 168 ...
Page 203: ... 194 ...
Page 363: ... 354 IX Troubleshooting GB HWE0913A ...
Page 365: ... 356 ...
Page 411: ......