
[
IX
Troubleshooting ]
- 238 -
HWE0913A
GB
1. Error
Code
High-pressure sensor fault (Outdoor unit HPS/BC controller PS1)
Intermediate pressure sensor fault (BC controller PS3)
2. Error definition and error detection method
When a pressure sensor reading of 4.06 MPa [589 psi] or above is detected, error codes "5201" and "5203" will appear.
The unit will continue its operation by using other sensors as a backup.
3. Cause, check method and remedy
5201
5203
Cause
Check method and remedy
(1)
High pressure sensor failure
Refer to the page on the troubleshooting of
the high pressure sensor.
(IX [4] -1-(page 288))
(2)
Pressure drop due to refrigerant leak
(3)
Torn wire coating
(4)
A pin on the male connector is missing or contact failure
(5)
Disconnected wire
(6)
High pressure sensor input circuit failure on the control board
Summary of Contents for PURY-P120TJMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 36: ... II Restrictions 27 HWE0913A GB ...
Page 50: ... II Restrictions 41 41 HWE0913A GB ...
Page 67: ... 58 II Restrictions GB HWE0913A ...
Page 69: ... 60 ...
Page 95: ... 86 III Outdoor Unit Components GB HWE0913A ...
Page 97: ... 88 ...
Page 105: ... 96 IV Remote Controller GB HWE0913A ...
Page 107: ... 98 ...
Page 125: ... 116 ...
Page 145: ... 136 ...
Page 175: ... 166 VII Control GB HWE0913A ...
Page 177: ... 168 ...
Page 203: ... 194 ...
Page 363: ... 354 IX Troubleshooting GB HWE0913A ...
Page 365: ... 356 ...
Page 411: ......