VIII
Test Run Mode ]
- 172 -
HWE0913A
GB
3. Amount of refrigerant to be added
The amount of refrigerant that is shown in the table below is factory-charged to the outdoor units.
The amount necessary for extended pipe (field piping) is not included and must be added on site.
(1) Calculation formula
The amount of refrigerant to be added depends on the size and the length of field piping. (unit in m[ft])
Round up the calculation result to the nearest 0.1kg. (Example: 18.04kg to 18.1kg)
Round up the calculation result in increments of 4oz (0.1kg) or round it up to the nearest 1oz. (Example: 78.21oz to 79oz)
Outdoor unit model
P72
P96
P120
P144
Amount of pre-charged refrigerant
in the outdoor unit (kg)
10.5
11.8
11.8
11.8
Amount of pre-charged refrigerant
in the outdoor unit [lbs-oz]
23-2
26-1
26-1
26-1
Amount of added refrigerant (kg) = (0.36 x L
1
) + (0.23 x L
2
) + (0.16 x L
3
) + (0.11 x L
4
)+ (0.2 x L
5
)
+ (0.12 x L
6
) + (0.06 x L
7
) + (0.024 x L
8
) +
ǩ
1
+
ǩ
2
+
ǩ
3
+
ǩ
4
Amount of added refrigerant (oz) = (3.88 x L
1
' ) + (2.48 x L
2
' ) + (1.73 x L
3
' ) + (1.19 x L
4
' )+ (2.16 x L
5
' )
+ (1.30 x L
6
' ) + (0.65 x L
7
' ) + (0.26 x L
8
' ) +
ǩ
1
' +
ǩ
2
' +
3
' +
ǩ
4
'
L
1
: Length of ø28.58[1-1/8"] high pressure pipe (m)
L
2
: Length of ø22.2[7/8"] high pressure pipe (m)
L
3
: Length of ø19.05[3/4"] high pressure pipe (m)
L
4
: Length of ø15.88[5/8"] high pressure pipe (m)
L
5
: Length of ø15.88[5/8"] liquid pipe (m)
L
6
: Length of ø12.7[1/2"] liquid pipe (m)
L
7
: Length of ø9.52[3/8"] liquid pipe (m)
L
8
: Length of ø6.35[1/4"] liquid pipe (m)
ǩ
1
,
ǩ
2
,
ǩ
3
,
ǩ
4
,
ǩ
1
' ,
ǩ
3
' ,
ǩ
4
' : Refer to the table below.
L
1
' : Length of ø28.58[1-1/8"] high pressure pipe [ft]
L
2
' : Length of ø22.2[7/8"] high pressure pipe [ft]
L
3
' : Length of ø19.05[3/4"] high pressure pipe [ft]
L
4
' : Length of ø15.88[5/8"] high pressure pipe [ft]
L
5
' : Length of ø15.88[5/8"] liquid pipe [ft]
L
6
' : Length of ø12.7[1/2"] liquid pipe [ft]
L
7
' : Length of ø9.52[3/8"] liquid pipe [ft]
L
8
' : Length of ø6.35[1/4"] liquid pipe [ft]
Outdoor unit total
index
Amount for the BC
controllers (main/sub)
BC controller (main)
Total capacity of
connected indoor
units
Amount for the Indoor
unit
ǩ
1
(kg)
ǩ
1
' (oz)
ǩ
4
(kg)
ǩ
4
' (oz)
P72 model
3.0
106
HA type
ǩ
2
(kg)
ǩ
2
' (oz)
-
27
2.0
71
P96 model
4.5
159
1
2.0 71
28
-
54
2.5
89
P120 model
55
-
126
3.0 106
P144 model
BC controller (sub)
127
-
144
3.5
124
P168 model
7.5
265
145
-
180
4.5
159
P192 model
9.0
318
Total number of BC
ǩ
3
(kg)
ǩ
3
' (oz)
181
-
234
5.0
177
P216 model
1
1.0
35
235
-
273
6.0
212
P240 model
2
2.0
71
274
-
307
8.0
283
P264 model
308
-
342
9.0
318
P288 model
343
-
411
10.0
353
412
-
12.0
424
Summary of Contents for PURY-P120TJMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 36: ... II Restrictions 27 HWE0913A GB ...
Page 50: ... II Restrictions 41 41 HWE0913A GB ...
Page 67: ... 58 II Restrictions GB HWE0913A ...
Page 69: ... 60 ...
Page 95: ... 86 III Outdoor Unit Components GB HWE0913A ...
Page 97: ... 88 ...
Page 105: ... 96 IV Remote Controller GB HWE0913A ...
Page 107: ... 98 ...
Page 125: ... 116 ...
Page 145: ... 136 ...
Page 175: ... 166 VII Control GB HWE0913A ...
Page 177: ... 168 ...
Page 203: ... 194 ...
Page 363: ... 354 IX Troubleshooting GB HWE0913A ...
Page 365: ... 356 ...
Page 411: ......