- 353 -
[
IX
Troubleshooting ]
[7] Collecting the Cooling Liquid from the Accumulator (Only P168-P234 types)
1) Perform evacuation inside the recovery cylinder.
2) Connect the check joint for collecting liquid that is derived from the accumulator and the recovery cylinder with a
connection pipe (or hose that has predetermined withstand pressure).
Note: When the check joint and the connecting pipe (hose) are connected, extremely low-temperature oil may
flow out. Use some protective clothing, such as leather gloves.
3) Open the valves of the recovery cylinder while the recovery cylinder is being weighed, and collect the liquid inside
the accumulator into the cylinder.
Note: Allow some capacity when collecting the refrigerant so that the recovery cylinder will not overflow. Use
several cylinders when collecting large amount of refrigerant.
4) After collecting the refrigerant, close the valve of the recovery cylinder, and remove the connecting pipe (hose).
Note: When the check joint and the connecting pipe (hose) are connected, extremely low-temperature oil may
flow out. Use some protective equipment, such as leather gloves.
5) Charge 3-liter oil from the check joint on the accumulator during evacuation.
No.1 Compressor
Soundproof material
No. 2 compressor
Oil balance
pipe joint
Metal fitting 1
Oil-equalizing pipe
Metal fitting 2
Flare Nut
Drain oil plug
Flare nut
Check joint for draining liquid
Summary of Contents for PUHY-P168
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 127: ... 118 ...
Page 145: ... 136 ...
Page 147: ... 138 ...
Page 185: ... 176 ...
Page 187: ... 178 ...
Page 241: ... 232 ...
Page 243: ... 234 ...
Page 366: ... 357 IX Troubleshooting ...
Page 367: ... 358 ...
Page 369: ... 360 ...