- 309 -
[
IX
Troubleshooting ]
4
"88" appears on the remote
controller when the address is
registered or confirmed.
An error occurs when the ad-
dress is registered or confirmed.
(common)
1. A wrong address is set to the unit
to be coupled.
2. The transmission line of the unit to
be coupled is disconnected or is
not connected.
3. Circuit board failure of the unit to
be coupled
4. Improper transmission line work
(1) Confirm the address of unit to be cou-
pled.
(2) Check the connection of transmission
line.
(3) Check voltage of the terminal block for
transmission line of the unit to be cou-
pled.
(i) Normal if voltage is between DC17
and 30V.
(ii) Check (4) in case other than i).
Generates at interlocking regis-
tration between LOSSNAY and
the indoor unit
5. The power of LOSSNAY is OFF.
(4) Check for the main power of LOSSNAY.
Generates at confirmation of con-
trollers used in the system in
which the indoor units connected
to different outdoor units are
grouped
6. The power of the outdoor unit to
be confirmed has been cut off.
7. The transmission line for central-
ized control (TB7) is disconnect-
ed.
8. When the indoor units connected
to different outdoor units are
grouped without MELANS, the
male power supply connector is
not connected to the female pow-
er supply switch connector
(CN40) for the transmission line
for centralized control.
9. The male power supply connec-
tors on 2 or more outdoor units
are connected to the female pow-
er supply switch connector
(CN40) for the transmission line
for centralized control.
10.In the system to which MELANS
is connected, the male power
supply connector is connected to
the female power supply switch
connector (CN40) for the trans-
mission line for centralized con-
trol.
11.Short circuit of the transmission
line for centralized control
(5) Check the power supply of the outdoor
unit which is coupled with the unit to be
confirmed.
(6) Check that the transmission line for
centralized control (TB7) of the out-
door unit is not disconnected.
(7) Check voltage of the transmission line
for centralized control.
(i) Normal when voltage is between
10V and 30V
(ii) Check 8 - 11 described on the left in
case other than i).
Phenomena
Cause
Summary of Contents for PUHY-P168
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 127: ... 118 ...
Page 145: ... 136 ...
Page 147: ... 138 ...
Page 185: ... 176 ...
Page 187: ... 178 ...
Page 241: ... 232 ...
Page 243: ... 234 ...
Page 366: ... 357 IX Troubleshooting ...
Page 367: ... 358 ...
Page 369: ... 360 ...