- 184 -
[
VIII
Test Run Mode ]
(2) Example: PUHY-P234TGMU-A
(3) Sample calculation
15.88 [3/4"](30 m [98 ft])
15.88 [3/4"](10 m [32 ft])
6.35 [1/4"]
(10 m [32 ft])
9.52 [3/8"](10 m [32 ft])
9.52 [3/8"]
(10 m [32 ft])
9.52 [3/8"]
(10m [32 ft])
9.52 [3/8"]
(20 m [65 ft])
9.52 [3/8"]
(20 m [65 ft])
96 model
54 model
30 model
24 model
06 model
All the pipes in the figure are liquid pipes.
15.88 [3/4"] : 30 m [98 ft] + 10 m [32 ft] = 40 m [130 ft]
9.52 [3/8"] : 10 m [32 ft] + 2 0m [65 ft] + 20 m [65 ft] + 10 m [32 ft] + 10 m [32 ft] = 70 m [226 ft]
6.35 [1/4"] : 10 m [32 ft]
According to the above formula
The calculation result would be 15.44, and it is rounded up to the nearest 0.1.
The calculation result would be 540.7oz, and it is rounded up to the nearest 1 oz or 4 oz.
The final result will be as follows:
Amount of refrigerant to be charged (kg) = (0.2 X 40) + (0.06 X 70) + (0.024 X 10) + 3 = 15.44kg
Amount of refrigerant to be charged = 15.5kg
The final result will be as follows:
Amount of refrigerant to be charged (oz) = (2.15 X 130) + (0.65 X 226) + (0.26 X 32) + 106 = 540.7oz
Amount of refrigerant to be charged = 544oz or 541oz
CAUTION
Charge liquid refrigerant (as opposed to gaseous refrigerant) into the system.
If gaseous refrigerant is charged into the system, the composition of the refrigerant in the cylinder will change and may
result in performance loss.
Summary of Contents for PUHY-P168
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 127: ... 118 ...
Page 145: ... 136 ...
Page 147: ... 138 ...
Page 185: ... 176 ...
Page 187: ... 178 ...
Page 241: ... 232 ...
Page 243: ... 234 ...
Page 366: ... 357 IX Troubleshooting ...
Page 367: ... 358 ...
Page 369: ... 360 ...