- 192 -
[
VIII
Test Run Mode ]
[7] Standard Operation Data (Reference Data)
1. PUHY <SI unit>
(1) Cooling operation
Operation
Outdoor unit model
PUHY-P72TGMU-A
PUHY-P96TGMU-A
Operat-
ing condi-
tions
Ambient
tempera-
ture
Indoor
DB/
WB
°C
26.7/19.4
26.7/19.4
Outdoor
35.0/- 35.0/-
Indoor
unit
No. of connected
units
Unit
4
4
No. of units in opera-
tion
4
4
Model
-
27
24
18
06
36
27
24
06
Piping
Main pipe
m
5
5
Branch pipe
10
10
Total pipe length
45
45
Fan speed
-
Hi
Hi
Amount of refrigerant
kg
11.0
13.9
Outdoor
unit
Electric current
A
19.9/18.0
26.7/24.1
Voltage
V
208/230
208/230
Compressor frequency
Hz
53
70
LEV
opening
Indoor unit
Pulse
253 441
362
187
325
253
441 187
SC (LEV1)
82
100
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
3.00/0.92
2.87/0.96
Temp. of
each sec-
tion
Outdoor
unit
Discharge
(TH11)
°C
84
86
Heat exchanger out-
let (TH5)
39
41
Accumu-
lator
Inlet
14
14
Outlet
14
14
Compressor inlet
27
23
Compressor shell
bottom
39
39
SC heat exchanger
outlet (TH7)
19
20
Bypass outlet (TH8)
10
11
Indoor
unit
LEV inlet
19
19
Heat exchanger
outlet
13
13
Summary of Contents for PUHY-P168
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 127: ... 118 ...
Page 145: ... 136 ...
Page 147: ... 138 ...
Page 185: ... 176 ...
Page 187: ... 178 ...
Page 241: ... 232 ...
Page 243: ... 234 ...
Page 366: ... 357 IX Troubleshooting ...
Page 367: ... 358 ...
Page 369: ... 360 ...