- 32 -
[
II
Restrictions ]
Address setting method
Pro
ce-
du-
res
Unit or controller
Address
setting
range
Setting method
Notes
Facto-
ry set-
ting
1
Indoor
unit
Main unit
IC
01 to 50
Assign the smallest address to the
main unit in the group.
In an R2 system with a sub BC
controller, make the settings for
the indoor units in the following or-
der.
(i) Indoor unit to be connected to
the main BC controller
(ii) Indoor unit to be connected to
sub BC controller 1
(iii) Indoor unit to be connected to
sub BC controller 2
Make the settings for the indoor
units in the way that the formula
"(i) < (ii) < (iii)" is true.
Port number setting is re-
quired by an R2 system.
00
Sub unit
Assign sequential numbers starting
with the address of the main unit in
the same group +1. (Main unit ad-
dress +1, main unit a2,
main unit a3, etc.)
2
LOSSNAY
LC
01 to 50
Assign an arbitrary but unique ad-
dress to each of these units after as-
signing an address to all indoor
units.
None of these addresses
may overlap any of the in-
door unit addresses.
00
3
MA
remote
controller
Main
remote
controller
MA
No
settings
required.
-
Main
Sub
remote
controller
MA
Sub
remote
controller
Settings to be made according to the
remote controller function selection
4
Outdoor unit
OC
51 to 100 The sum of the smallest address of
the indoor units in the same system
and 50
To set the address to 100,
set it to 50.
00
5
Auxiliary
unit
BC
controller
(main)
BC
52 to 100 Outdoor unit a 1
To set the address to
100, set it to 50.
If a given address over-
laps any of the address-
es that are assigned to
the outdoor units or to
the sub BC controller,
use a different, unused
address within the set-
ting range.
The use of a sub BC
controller requires the
connection of a main
BC controller.
00
BC
controller
(sub)
BS
Assign an address that equals the
sum of the smallest address of the
indoor units that are connected to
the sub BC controller and 50.
Summary of Contents for PUHY-P168
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 127: ... 118 ...
Page 145: ... 136 ...
Page 147: ... 138 ...
Page 185: ... 176 ...
Page 187: ... 178 ...
Page 241: ... 232 ...
Page 243: ... 234 ...
Page 366: ... 357 IX Troubleshooting ...
Page 367: ... 358 ...
Page 369: ... 360 ...