- 127 -
[
VI
Refrigerant Circuit ]
Ther-
mistor
TH11
TH12
(Discharge)
TH12 is
available
only on
P168-
P234
models
1. Detects discharge air temper-
ature
2. Provides high-pressure pro-
tection
Resis-
tance
check
0°C[32°F] :698kohm
10°C[50°F] :413kohm
20°C[68°F] :250kohm
30°C[86°F] :160kohm
40°C[104°F] :104kohm
50°C[122°F] : 70kohm
60°C[140°F] : 48kohm
70°C[158°F] : 34kohm
80°C[176°F] : 24kohm
90°C[194°F] :17.5kohm
100°C[212°F] :13.0kohm
110°C[230°F] : 9.8kohm
TH5
(Pipe
temperature)
1. Controls frequency
2. Controls defrosting during
heating operation
3. Detects subcool at the heat
exchanger outlet and controls
LEV1 based on HPS data and
TH5 data
0°C[32°F] :15kohm
10°C[50°F] :9.7kohm
20°C[68°F] :6.4kohm
25°C[77°F] :5.3kohm
30°C[86°F] :4.3kohm
40°C[104°F] :3.1kohm
Resis-
tance
check
TH6
(Outdoor
temperature)
1. Detects outdoor air tempera-
ture
2. Controls fan operation
TH7
TH8
Controls LEV1 based on TH5,
TH7, and TH8 data.
THHS
Inverter
heat sink
temperature
Heat sink Controls inverter cooling fan
based on THHS temperature
0°C[32°F] :181kohm
10°C[50°F] :105kohm
20°C[68°F] :64kohm
25°C[77°F] :50kohm
30°C[86°F] :40kohm
40°C[104°F] :26kohm
Solenoid
valve
SV1
Discharge-
suction
bypass
1. High/low pressure bypass at
start-up and stopping, and ca-
pacity control during low-load
operation
2. High-pressure-rise prevention
AC208/230V
Open while being powered/
closed while not being pow-
ered
Continuity
check with
a tester
SV3
Discharge-
suction
bypass
P168-
P234
models
only
Provides compressor protection
while compressor No. 2 is
stopped
SV5b
Heat
exchanger
capacity
control
P126-
P234
models
only
Controls outdoor unit heat ex-
changer capacity
AC208/230V
Closed while being powered/
open while not being powered
Part
name
Symbols
(functions)
Notes
Usage
Specifications
Check
method
R = 7.465k
120
R = 4057
R =
7.465
25/120
t
4057 273 t
1
393
1
exp
R = 15k
0
R = 3460
R = 15
0/80
t
3460 273 t
1
273
1
exp
R = 17k
50
R = 4170
R = 17
25/120
t
4170
273 t
1
323
1
exp
Summary of Contents for PUHY-P168
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 127: ... 118 ...
Page 145: ... 136 ...
Page 147: ... 138 ...
Page 185: ... 176 ...
Page 187: ... 178 ...
Page 241: ... 232 ...
Page 243: ... 234 ...
Page 366: ... 357 IX Troubleshooting ...
Page 367: ... 358 ...
Page 369: ... 360 ...