- 224 -
[
VIII
Test Run Mode ]
Operation
Outdoor unit model
Model name of BC controller
PURY-P144TGMU-A
CMB-P108NU-GA
PURY-P168TGMU-A
CMB-P108NU-GA
Operat-
ing condi-
tions
Power supply
V
208/230
208/230
Ambient
tempera-
ture
Indoor
DB/
WB
°F
80/67
80/67
Outdoor
95/-
95/-
Indoor
unit
No. of connect-
ed units
Unit
4
4
No. of units in
operation
4
4
Model
-
72
36
24
12
96
36
24
12
Piping
Main pipe
Ft
16
16
Branch pipe
32
32
Total pipe length
147
147
Fan speed
-
Hi
Hi
Amount of refrigerant
lbs-
oz
48-15
61-1
Outdoor
unit
Electric current
A
43.8/39.6
46.1/41.7
Voltage
V
208/230
208/230
Compressor frequency
(No.1 / No.2)
Hz
103
65/60
LEV
opening
Indoor unit
Pulse
324 325
441
261
324
387
275 362
BC controller (1/2/3)
2000/2000/180
2000/2000/190
Pressure
High pressure/low pressure
psi
422/136
399/125
BC controller on the liquid
side/Intermediate part
400/400
377/377
Temp. of
each sec-
tion
Outdoor
unit
Discharge
(TH11/TH12)
°F
187/-
180/185
Heat exchanger
outlet (TH5)
113
106
Accumu-
lator
Inlet
61
59
Out-
let
61
59
Compressor
inlet
73
70/81
Compressor
shell bottom
118
91/108
Indoor
unit
LEV inlet
79
75
Heat exchanger
outlet
59
55
Summary of Contents for PUHY-P168
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 127: ... 118 ...
Page 145: ... 136 ...
Page 147: ... 138 ...
Page 185: ... 176 ...
Page 187: ... 178 ...
Page 241: ... 232 ...
Page 243: ... 234 ...
Page 366: ... 357 IX Troubleshooting ...
Page 367: ... 358 ...
Page 369: ... 360 ...