- 206 -
[
VIII
Test Run Mode ]
Operation
Outdoor unit model
PUHY-P216TGMU-A
PUHY-P234TGMU-A
Operat-
ing condi-
tions
Ambient
tempera-
ture
Indoor
DB/
WB
°F
80/67
80/67
Outdoor
95/- 95/-
Indoor
unit
No. of connected
units
Unit
5 5
No. of units in opera-
tion
5 5
Model
-
72
72
48
18
08
96
72
48
18
08
Piping
Main pipe
Ft
16 16
Branch pipe
32
32
Total pipe length
180
180
Fan speed
-
Hi
Hi
Amount of refrigerant
lbs-
oz
62-6 64-9
Outdoor
unit
Electric current
A
61.4/55.5
66.6/60.3
Voltage
V
208/230
208/230
Compressor frequency
(No.1/No.2)
Hz
98/60
107/60
LEV
opening
Indoor unit
Pulse
324 324 387 362 222 388 324 387 362 222
SC (LEV1)
246
266
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
psi
425/122 439/120
Temp. of
each sec-
tion
Outdoor
unit
Discharge
(TH11/TH12)
°F
183/187 187/187
Heat exchanger out-
let (TH5)
106 109
Accumu-
lator
Inlet
59
57
Outlet
59
57
Compressor inlet
66/63
64/59
Compressor shell
bottom
117/109
127/120
SC heat exchanger
outlet (TH7)
75
79
Bypass outlet (TH8)
46
45
Indoor
unit
LEV inlet
75
75
Heat exchanger
outlet
54
54
Summary of Contents for PUHY-P168
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 127: ... 118 ...
Page 145: ... 136 ...
Page 147: ... 138 ...
Page 185: ... 176 ...
Page 187: ... 178 ...
Page 241: ... 232 ...
Page 243: ... 234 ...
Page 366: ... 357 IX Troubleshooting ...
Page 367: ... 358 ...
Page 369: ... 360 ...