- 132 -
[
VI
Refrigerant Circuit ]
2. Indoor unit
Part
name
Symbols
(functions)
Notes
Usage
Specifications
Check method
Linear ex-
pansion
valve
(LEV)
LEV
1.Adjusts superheat at the heat
exchanger outlet of the indoor
unit during cooling
2.Adjusts subcool at the heat
exchanger outlet of the indoor
unit during cooling
DC12V
Opening of a valve driven by
a stepping motor
0-(1400) pulses
Refer to the sec-
tion "
Ⅸ
[4] -6-
LEV".
Continuity be-
tween white, red,
and orange.
Continuity be-
tween yellow,
brown, and blue.
Ther-
mistor
TH1
(Suction
air tem-
perature)
Indoor unit control (Thermo)
0°C[32°F] : 15kohm
10°C[50°F] :9.7kohm
20°C[68°F] :6.4kohm
25°C[77°F] :5.3kohm
30°C[86°F] :4.3kohm
40°C[104°F] :3.1kohm
Resistance check
TH2
(Pipe tem-
perature)
1.Indoor unit control (Freeze
prevention, Pre-heating
stand-by)
2.LEV control during heating
operation (Subcool detection)
TH3
(Gas pipe
tempera-
ture)
LEV control during cooling oper-
ation (Superheat detection)
TH4
(Outdoor
tempera-
ture)
Indoor unit control (Thermo)
Tempera-
ture
sensor
(Indoor
tempera-
ture)
Indoor unit control (Thermo)
Yellow
M
Blue
Brown
White
Red
Orange
R = 15k
0
R = 3460
R = 15
0/80
t
3460 273 t
1
273
1
exp
Summary of Contents for PUHY-P168
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 127: ... 118 ...
Page 145: ... 136 ...
Page 147: ... 138 ...
Page 185: ... 176 ...
Page 187: ... 178 ...
Page 241: ... 232 ...
Page 243: ... 234 ...
Page 366: ... 357 IX Troubleshooting ...
Page 367: ... 358 ...
Page 369: ... 360 ...