- 199 -
[
VIII
Test Run Mode ]
Operation
Outdoor unit model
PUHY-P144TGMU-A
PUHY-P168TGMU-A
Operat-
ing condi-
tions
Ambient
tempera-
ture
Indoor
DB/
WB
°C
21.1/-
21.1/-
Outdoor
8.3/6.1
8.3/6.1
Indoor
unit
No. of connected
units
Unit
4
4
No. of units in op-
eration
4
4
Model
-
72
36
24
12
72
48
30
18
Piping
Main pipe
m
5
5
Branch pipe
10
10
Total pipe length
45
45
Fan speed
-
Hi
Hi
Amount of refrigerant
kg
18.2
21.6
Outdoor
unit
Electric current
A
42.1/38.1
46.3/41.9
Voltage
V
208/230
208/230
Compressor frequency
(No.1/No.2)
Hz
103
62/60
LEV
opening
Indoor unit
Pulse
332
332
455
254
332
406
280
373
SC (LEV1)
-
-
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
2.43/0.68 2.83/0.69
Temp. of
each sec-
tion
Outdoor
unit
Discharge
(TH11/TH12)
°C
71
75/78
Heat exchanger
outlet (TH5)
2
4
Accumu-
lator
Inlet
0
1
Outlet
0
1
Compressor inlet
-1
1/1
Compressor shell
bottom
30
23/27
Indoor
unit
LEV inlet
31
38
Heat exchanger
outlet
67
71
Summary of Contents for PUHY-P168
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 127: ... 118 ...
Page 145: ... 136 ...
Page 147: ... 138 ...
Page 185: ... 176 ...
Page 187: ... 178 ...
Page 241: ... 232 ...
Page 243: ... 234 ...
Page 366: ... 357 IX Troubleshooting ...
Page 367: ... 358 ...
Page 369: ... 360 ...