- 153 -
[
VII
Control ]
-8- Defrost Operation Control <PURY>
(1) Starting the defrost operation
Defrost operation is started when the pipe temperature (TH5) of -10°C [14°F] or below (-8°C [18°F] or below for P126-
type and above) has continuously been detected for 3 minutes after the integrated compressor operation time of 50 min-
utes have passed (90 minutes when the defrost prohibit timer is set to 90 minutes).
If 10 minutes have passed since compressor start-up or since the completion of defrost operation, forced defrost opera-
tion will start by turning on the forced defrost switch (DIP SW2-7).
Even if the defrost prohibit timer is set to 90 minutes, the actual defrost prohibit time for the next operation will be 50
minutes if defrosting took 12 minutes.
(2) Defrost operation
(3) Stopping the defrost operation
Defrost operation will stop when 12 minutes have passed since the beginning of defrost operation or when the piping
temperature (TH5 and TH7) of 10°C [50°F] or above has been continuously detected for 2 min (15°C [59°F] or above for
8 minutes for P168 model and later).
(4) Problems during defrost operation
If a problem is detected during defrost operation, the operation will be stopped, and the defrost prohibition time based on
the integrated compressor operation time will be set to 20 minutes.
(5) Change in the number of operating indoor units during defrost operation
Even when there is a change in the number of operating indoor units during defrost operation, the operation will continue,
and an adjustment will be made after the completion of the defrost operation.
Defrost operation will be continued, even if the indoor units stop or under the Thermo-OFF conditions until it has run its
course.
Compressor frequency
Model
No.1 Compressor
No.2 Compressor
P72 model
52
-
P96 model
65
-
P108 model
65
-
P126 model
114
-
P144 model
114
-
P168 model
(50/60 Hz)
110/100
ON (50/60 Hz)
P192 model
(50/60 Hz)
110/100
ON (50/60 Hz)
P204 model
(50/60 Hz)
110/100
ON (50/60 Hz)
P216 model
(50/60 Hz)
110/100
ON (50/60 Hz)
P234 model
(50/60 Hz)
110/100
ON (50/60 Hz)
Outdoor unit fan
Stopped
SV1 ON
SV2
ON
SV3
(P168-P234 models only)
ON
21S4a OFF
21S4b
(P144-P234 models only)
OFF
BC controller LEV12
G type: 4000, GA type: 6000
BC controller LEV34
G type: 1000, GA type: 2000
BC controller LEV3a
60 (Fully open)
BC controller SVM1
ON
BC controller SVM2
OFF
Summary of Contents for PUHY-P168
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 127: ... 118 ...
Page 145: ... 136 ...
Page 147: ... 138 ...
Page 185: ... 176 ...
Page 187: ... 178 ...
Page 241: ... 232 ...
Page 243: ... 234 ...
Page 366: ... 357 IX Troubleshooting ...
Page 367: ... 358 ...
Page 369: ... 360 ...