- 246 -
[
IX
Troubleshooting ]
4108
Overcurrent
protection
1. First detection
If 51C2 is started dur-
ing the operation of
No.2 compressor, the
outdoor unit stops
once, turns to anti-re-
start mode for 3 min-
utes, and restarts after
3 minutes. (Set value
of the over-current re-
lay: 43A)
2. Second detection
If 51C2 is started
again within a minute
after restarting in com-
pliance with 1. above,
the unit makes an er-
ror stop and the error
code "4108" will ap-
pear.
3. There will be a minute
grace period of an er-
ror stop when No.2
compressor restarts
after the outdoor unit
stops and LED indi-
cates, which means
the grace period, will
appear.
(1) Overload operation that
exceeds unit use limit
Check the unit working condition.
(2) Power supply error
Power-supply voltage
drop
Open phase of power
supply voltage
Check the voltage of the power sup-
ply terminal block (TB1).
Check for open phase.
(3) Faulty wiring
Check 52C2 connector and the wir-
ing.
(4) Compressor failure
Compressor open phase
or grounding fault
Compressor lock
Check the wiring and apply a meg-
ger to the compressor.
Start operation under no-load condi-
tions.
Remove the power wire on the com-
pressor-side, insulate the power line
and start operation.
-> The compressor is faulty if
52C2 normally turns on.
4115
Power supply
sync signal ab-
normality
The frequency cannot be
determined when the
power is switched on.
(1) Power supply error
Check the voltage of the power sup-
ply terminal block (TB1).
(2) A fuse is blown
Check the fuses on the main board
(F01 and F02).
(3) Faulty wiring
Measure voltages of pin 5 of the
male connector (CN20) on the main
board and between pins 1 and 3 of
the male connector (CN21) on the
main board.
If the voltage (AC208/230V) is not
the same as the power supply volt-
age, the wiring is faulty.
(4) Main board failure
If none of the items described above
is applicable, and if the trouble reap-
pears even after the power is
switched on again, replace the MAIN
board.
4116
Motor abnor-
mality
1. LOSSNAY
The motor keep running
even if the power is OFF.
The thermal overload re-
lay is ON. (Only for the
three-phase model)
2. Indoor unit
If detected less than
180rpm or more than
2000rpm, the indoor
unit will restart and
keep running for 3
minutes.If detected
again, the display will
appear.
(1) Board failure
Replace the board.
(2) Motor malfunction
(3) Solenoid switch malfunc-
tion
Check for the motor and the solenoid
switch.
Error Code
Error definition and error
detection method
Cause
Check method and remedy
Summary of Contents for PUHY-P168
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 127: ... 118 ...
Page 145: ... 136 ...
Page 147: ... 138 ...
Page 185: ... 176 ...
Page 187: ... 178 ...
Page 241: ... 232 ...
Page 243: ... 234 ...
Page 366: ... 357 IX Troubleshooting ...
Page 367: ... 358 ...
Page 369: ... 360 ...