- 292 -
[
IX
Troubleshooting ]
(3) System connected to the system controllers (MELANS)
Error Code
Error definition and error detection method
6607
(Contin-
ued)
No ACK abnormality
The error is detected when no acknowledgement (ACK signal) is received after the
transmission. (eg. When the data is transmitted six times in a row with 30 seconds
interval, the error is detected on the transmission side.)
Note: The address/attribute appeared on the display on the remote controller
indicates the controller which did not provide the response (ACK).
Error
source ad-
dress
Error dis-
play
Detection
method
Cause
Check method and remedy
Outdoor
unit
(OC)
M-NET re-
mote control-
ler (RC)
System con-
troller (SC)
MA remote
controller
(MA)
No ac-
knowl-
edgement
(ACK) at
BC trans-
mission to
OC
Same cause as that for system with
one outdoor unit
Same remedy as that for system with one
outdoor unit
BC control-
ler (BC)
M-NET re-
mote control-
ler (RC)
system con-
troller (SC)
MA remote
controller
(MA)
No ac-
knowl-
edgement
(ACK) at IC
transmis-
sion to BC
Same cause as that for system with
one outdoor unit
Same remedy as that for system with one
outdoor unit
Indoor
unit
(IC)
M-NET re-
mote con-
troller (RC)
No acknowl-
edgement
(ACK) at RC
transmission
to IC
Same as grouping of units in a sys-
tem with multiple outdoor units
Same remedy as that for grouping of units in
a system with multiple outdoor units
system
controller
(SC)
No ac-
knowl-
edgement
(ACK) at
SC trans-
mission to
IC
1. Error occurrence on some IC
(1) Same cause as that for system
with one outdoor unit
Same remedy as that for system with
one outdoor unit
2. Error occurrence on all IC in the
system with one outdoor unit
(1) Total capacity error (7100)
(2) Capacity code error (7101)
(3) Error in the number of connected units
(7102)
(4) Address setting error (7105)
(5) Disconnection or short circuit of the
transmission line for the outdoor unit
on the terminal block for centralized
control line connection (TB7)
(6) Turn off the power source of the out-
door unit
(7) Malfunction of electrical system for the
outdoor unit
1) Check the LED display for troubleshoot-
ing on the outdoor unit.
->If an error is found, check the check
code definition, and correct the error.
->If no error is found, check 2).
2) Check (5) - (7) on the left.
3. Error occurrence on all IC
(1) Same causes as (1) - (7) described in
2.
(2) The male power supply connectors on
2 or more outdoor units are connected
to the female power supply switch con-
nector (CN40) for the transmission line
for centralized control.
(3) Disconnection or shutdown of the pow-
er source of the power supply unit for
transmission line
(4) System controller (MELANS) malfunc-
tion
Check voltage of the transmission line for
centralized control.
20V or more : Check (1) and (2) on the
left.
Less than 20V : Check (3) on the left.
Summary of Contents for PUHY-P168
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 127: ... 118 ...
Page 145: ... 136 ...
Page 147: ... 138 ...
Page 185: ... 176 ...
Page 187: ... 178 ...
Page 241: ... 232 ...
Page 243: ... 234 ...
Page 366: ... 357 IX Troubleshooting ...
Page 367: ... 358 ...
Page 369: ... 360 ...