Troubleshooting ]
(2) In case of M-NET remote controller
Phenomena
Cause
Check method and remedy
1
Even if the operation button on
the remote controller is
pressed, the display remains
unlit and the unit does not start
running.
(Power indicator does not
appear on the screen.)
1.The power for the M-NET trans-
mission line is not supplied from
the outdoor unit.
2.Short circuit of the transmission
line.
3.Incorrect wiring of the M-NET
transmission line on the outdoor
unit.
Disconnected wire for the MA re-
mote controller or disconnected
line to the terminal block.
The indoor transmission line is
connected incorrectly to the
transmission terminal block for
centralized controller (TB7).
4.Disconnected transmission line
on the remote controller.
5.Remote controller failure
Check voltage of the transmission terminal
block for of the M-NET remote controller.
(1) If voltage between is 17V and 30V
-> M-NET remote controller failure
(2) When voltage is 17V or less
-> Refer to 9. [4].7.(2) "Outdoor unit
transmission power source circuit
failure judgment".
When 2. and 3. apply, check code 7102
will be displayed on the self-diagnosis
LED.
Summary of Contents for PUHY-P168
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 127: ... 118 ...
Page 145: ... 136 ...
Page 147: ... 138 ...
Page 185: ... 176 ...
Page 187: ... 178 ...
Page 241: ... 232 ...
Page 243: ... 234 ...
Page 366: ... 357 IX Troubleshooting ...
Page 367: ... 358 ...
Page 369: ... 360 ...