- 207 -
[
VIII
Test Run Mode ]
(2) Heating operation
Operation
Outdoor unit model
PUHY-P72TGMU-A PUHY-P96TGMU-A
Operat-
ing condi-
tions
Ambient
tempera-
ture
Indoor
DB/
WB
°F
70/-
70/-
Outdoor
47/43
47/43
Indoor
unit
No. of connected
units
Unit
4
4
No. of units in op-
eration
4
4
Model
-
27
24
18
06
36
27
24
06
Piping
Main pipe
Ft
16
16
Branch pipe
32
32
Total pipe length
147
147
Fan speed
-
Hi
Hi
Amount of refrigerant
lbs-
oz
24-4
30-12
Outdoor
unit
Electric current
A
19.5/17.6
26.4/23.8
Voltage
V
208/230
208/230
Compressor frequency
Hz
55
73
LEV
opening
Indoor unit
Pulse
259
455
373
194
332
259
455
194
SC (LEV1)
-
-
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
psi
409/97 392/94
Temp. of
each sec-
tion
Outdoor
unit
Discharge
(TH11)
°F
174
169
Heat exchanger
outlet (TH5)
34
34
Accumu-
lator
Inlet
32
32
Outlet
32
32
Compressor inlet
54
34
Compressor shell
bottom
163
73
Indoor
unit
LEV inlet
100
95
Heat exchanger
outlet
165
162
Summary of Contents for PUHY-P168
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 127: ... 118 ...
Page 145: ... 136 ...
Page 147: ... 138 ...
Page 185: ... 176 ...
Page 187: ... 178 ...
Page 241: ... 232 ...
Page 243: ... 234 ...
Page 366: ... 357 IX Troubleshooting ...
Page 367: ... 358 ...