- 322 -
[
IX
Troubleshooting ]
(7) In case of SV5b (2-way switching valve) (only for P126-P234 models)
This 2-way valve is closed when powered. Check the LED display and the switching sound to check whether the valve
has no faults.When cooling, the switching coincides with 21S4b. When it is difficult to check by the sound, check the tem-
perature at the front and the back of the pipe to check whether the refrigerant is flowing.
∗
Do not give an impact from the outside, as the outer hull will be deformed, leading to the malfunction of the inner valve.
Tightening torque : 150N m
Plunger
Cap
Pin-face tool
Pin-face tool
1
2
3
4
5
6
Solenoid valve block 1
Solenoid valve block 2
Valve
BV2
ST1 BV1
CV8a
CV10a
CV9a
CV5a
CV4a
CV2a
CV3a
CV6a
CV7a
TH6
TH7
TH5
SV4a
SV4b
SV4c
SV4d
SV5a
SV5b
CV2b
CV5b
CV4b
CV6b
Orifice
ST14
HEXb1
HEXf1
HEXf2
HEXf3
ST15
ST16
ST17
ST18
ST19
HEXb2 HEXf4
Check Valves Block 1
Solenoid Valves Block 1
Solenoid Valves Block 2
Check Valves Block 2
CV7b
CV3b
Refrigerant Circuit Figure (P168 ~ P234 models)
Summary of Contents for PUHY-P168
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 127: ... 118 ...
Page 145: ... 136 ...
Page 147: ... 138 ...
Page 185: ... 176 ...
Page 187: ... 178 ...
Page 241: ... 232 ...
Page 243: ... 234 ...
Page 366: ... 357 IX Troubleshooting ...
Page 367: ... 358 ...
Page 369: ... 360 ...