- 155 -
[
VII
Control ]
-11- Capacity Control of Outdoor Fan and Heat Exchanger <PUHY>
(1) Control method
Depending on the capacity required, the rotation speed of the outdoor unit fan is controlled by the inverter, targeting a
constant evaporation temperature of (0°C [32°F]= 0.71 MPa [103 psi]) during cooling operation and constant condensing
temperature of (49°C [120°F]= 2.88 MPa [418 psi]) during heating operation.
The capacity of the heat exchanger on the P126-234 models of outdoors is controlled by the 4-way valve (21S4b) or the
solenoid valve (SV5b).
(2) Control
Outdoor unit fan stops while the compressor is stopped (except in the presence of input from snow sensor).
The fan operates at full speed for 5 seconds after start-up.
The outdoor unit fan stops during defrost operation.
(3) Capacity control of outdoor heat exchanger
Notes:
The unit runs a cooling cycle when 21S4b is not powered and runs a heating cycle when it is powered.
SV5b is open when it is not powered and is closed when it is powered.
While the unit is stopped, 21S4b is not powered cooling cycle, and SV5b is open.
-12- Capacity Control of Outdoor Fan and Heat Exchanger <PURY>
(1) Control method
Depending on the capacity required, the rotation speed of the outdoor unit fan is controlled by the inverter, targeting a
constant evaporation temperature of (0°C [32°F]= 0.71 MPa [103 psi]) during cooling operation and constant condensing
temperature of (49°C [120°F]= 2.88 MPa [418 psi]) during heating operation.
(2) Control
Outdoor unit fan stops while the compressor is stopped (except in the presence of input from snow sensor).
The fan operates at full speed for 5 seconds after start-up.
The outdoor unit fan stops during defrost operation.
[P126, P144 models]
Operation
mode
Heat exchanger
capacity
Inverter control
Notes
Cooling
50%
5-100%
21S4b ON, SV5b ON
100%
10-100%
21S4b OFF, SV5b OFF
Heating
100%
10-100%
21S4b ON, SV5b OFF
Defrost
100% 0%
21S4b OFF, SV5b OFF
[P168-P234 models]
Operation
mode
Heat exchanger
capacity
Number of fans
Inverter control
Notes
Cooling
50%
1
5 -100%
21S4b ON
SV5b ON
100% 2 10
-100%
21S4b
ON
SV5b ON
Heating
100% 2 10
-100%
21S4b
OFF
SV5b OFF
Defrost
100% 0
0%
21S4b
ON
SV5b OFF
Summary of Contents for PUHY-P168
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 127: ... 118 ...
Page 145: ... 136 ...
Page 147: ... 138 ...
Page 185: ... 176 ...
Page 187: ... 178 ...
Page 241: ... 232 ...
Page 243: ... 234 ...
Page 366: ... 357 IX Troubleshooting ...
Page 367: ... 358 ...
Page 369: ... 360 ...