- 172 -
[
IX
Troubleshooting ]
Select the "Inspection" mode using the "Normal/Inspection" switching switch on the indoor unit.
In "Inspection" mode, the local operation is enabled, and the remote ON/OFF operation
(external input or central manipulator) is disabled. If no external input is available, the local
operation is enabled in both "Normal" and "Inspection" modes.
The occurred error is not reported to the upper system, such as building management system
including central manipulator. (If an error occurs during inspection, the occurred error is reported
only to the units, and the error history remains on the units.)
Select the "OFF" mode using the MA remote controller of the indoor unit to stop the unit.
Turn OFF the power source of the indoor unit as necessary based on the inspection item.
(If the power source of the outdoor unit is turned OFF, the transmission error will be detected on the
central manipulator, and this is not abnormal.)
* To check the LEV operation, the inspection must be performed unit operation.
The LEV opening and the piping temperature behind the LEV can be monitored on the outdoor unit LED.
Check that the piping temperature changes normally depending on the LEV opening.
Check whether an error history remains on the nonvolatile memory on the indoor and outdoor units.
If an error history remains, take out the data before an error occurs, and correct the error after analyzing
the causes.
Check each component based on the maintenance/inspection items described on the previous page.
If problems are found, repair the component.
Delete the error code history recorded on the nonvolatile memory on the unit after the inspection.
(To delete the error history on the indoor and the outdoor units, turn the DipSW 2-3 on the outdoor unit that
is being powered from OFF to ON.) If the power source of the outdoor unit is turned OFF during inspection,
the transmission error detected by the central manipulator after the power recovery will be deleted.
(Do not turn OFF the power source of the outdoor unit until the inspection of all the units is completed,
as all the error history remained on the central manipulator will be deleted.
If no central manipulator is available, this operation is not necessary.)
*The transmission error detected by the central manipulator during power failure of the outdoor
unit will be reset automatically after the power recovers and after the transmission recovers normally.
Select the "ON" mode using the MA remote controller of the indoor unit to operate the unit.
Select the "Normal" mode using the using the "Normal/Inspection" switching switch on the indoor unit.
Completed
(4) Check method
1
2
3
4
5
6
7
8
Summary of Contents for PU(H)Y-P250YGM-A
Page 9: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 41: ... 32 ...
Page 53: ... 44 ...
Page 67: ... 58 ...
Page 73: ... 64 ...
Page 81: ... 72 ...
Page 83: ... 74 ...
Page 105: ... 96 ...
Page 107: ... 98 ...
Page 117: ... 108 ...
Page 119: ... 110 ...
Page 183: ... 174 ...