- 139 -
[
IX
Troubleshooting ]
Phenomena
Cause
3
"HO" display on the remote
controller does not disappear,
and no operation is performed
even if the button is pressed.
1.The power for the M-NET transmission line is not supplied from the outdoor unit.
(i) The main power of the outdoor unit is not turned on.
(ii) The connector on the circuit board of the outdoor unit is disconnected.
Main circuit board:CNS1, CNVCC3
INV circuit board:CNDC2, CNVCC2, CNL2
Gate-amp board:CNDC1
(iii) The power supply circuit of the outdoor unit is faulty.
Blown fuse (F01) on the G/A board
Damaged diode stack
Faulty INV circuit board
Damaged rush current protection resistor (R11, R12)
2.Short circuit of the transmission line.
3.Incorrect wiring of the M-NET transmission line on the outdoor unit.
Disconnected wire or disconnected line to the terminal block.
The indoor transmission line is connected incorrectly to the transmission
terminal block for centralized controller (TB7).
4.Disconnected M-NET transmission line on the indoor unit side.
5.Disconnected wire between the terminal block for M-NET line (TB5) of the indoor
unit and the indoor unit board (CN2M) or disconnected connector.
6.Incorrect wiring for the MA remote controller
Short-circuited wire for the MA remote controller
Disconnected wire for the MA remote controller (No.2) and disconnected
line to the terminal block.
Reversed daisy-chain connection between groups
Incorrect wiring for the MA remote controller to the terminal block for trans-
mission line connection (TB5) on the indoor unit
The M-NET transmission line is connected incorrectly to the terminal block
(TB15) for the MA remote controller.
7.The address of the outdoor unit is "the address of the indoor unit + 50 or more".
8.The address of the indoor unit is 51 or more.
9.The sub/main setting of the MA remote controller is set to sub.
10.Indoor unit board failure (MA remote controller communication circuit)
11.Remote controller failure
(1) If the causes 1-4 apply, LED5 (M-NET transmission voltage display) on the in-
door controller circuit board will be turned off.
(2) When 2, 3, and 5. apply, error code 7102 will be displayed on the self-diagnosis
LED.
Check method and remedy
YES
YES
YES
NO
NO
YES
YES
NO
NO
Check the self-diagnosis LED
Error found?
Error found?
Replace the M-NET remote
controller with the MA
remote controller
Check for 5, 6, 8 and 9.
9 ~ 12 V?
Same symptom for all units in a
system with one outdoor unit?
Check (1).
Check
2, 3 and 6.
Check 4.
Correct
the error.
Correct
the error.
Measure voltages of the
terminal block for transmission
line (TB15) on the indoor unit.
Refer to [4] -6- (2) "Outdoor unit transmission power source
circuit failure judgment" for the check method.
Is the error code 7102
displayed?
Indoor unit board or
MA remote controller failure
Summary of Contents for PU(H)Y-P250YGM-A
Page 9: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 41: ... 32 ...
Page 53: ... 44 ...
Page 67: ... 58 ...
Page 73: ... 64 ...
Page 81: ... 72 ...
Page 83: ... 74 ...
Page 105: ... 96 ...
Page 107: ... 98 ...
Page 117: ... 108 ...
Page 119: ... 110 ...
Page 183: ... 174 ...