- 125 -
[
IX
Troubleshooting ]
Temperature sensor failure (indoor unit)
Error Code
Error definition and error
detection method
Cause
Check method and remedy
5101
Air inlet
If a short or an open is
detected during thermo-
stat ON, the outdoor unit
turns to anti-restart mode
for 3 minutes. When the
error is not restored after
3 minutes (if restored, the
outdoor unit runs normal-
ly), the outdoor unit
makes an error stop.
Short:
detectable at
90°C or higher
Open :
detectable at
-40°C or lower
*Sensor error at gas-side
cannot be detected un-
der the following condi-
tions.
During heating oper-
ation
During cooling
operation for 3
minutes after the
compressor turns
on.
(1) Thermistor failure
(2) Connector contact failure
(3) Disconnected wire or par-
tial disconnected ther-
mistor wire
(4) Unattached thermistor or
contact failure
Check the thermistor resistor.
0°C : 15 kohm
10°C : 9.7 kohm
20°C : 6.4 kohm
30°C : 4.3 kohm
40°C : 3.1 kohm
5102
Liquid pipe
5103
Gas pipe
5104
Air outlet
(5) Indoor board (detection
circuit) failure
Check the connector contact.
When no fault is found, the indoor
board is a failure.