- 22 -
[
II
Restrictions ]
[4] An Example of a System to which an MA Remote Controller is connected
1. System with one refrigerant
Sample control wiring
Notes
Maximum allowable length
1.Leave the male connector on the female power supply
switch connector (CN41) on the outdoor unit as it is.
2.It is not necessary to provide grounding to S terminal on the
terminal block for transmission line for centralized control
(TB7).
3.Although two indoor controllers (controller circuit boards)
are equipped inside the indoor unit, the board on No.2 side
(lower side) is not used. Do not connect wiring to the lower
controller circuit board.
(1) Indoor/outdoor transmission line
Maximum distance (1.25mm
2
or larger)
L1
200m
NO
*Two indoor controllers (controller circuit boards)
are equipped in the indoor unit (P500).
OC
TB3
TB7
M1M2
M1M2 S
51
IC
TB5-1
A1 B1S
01
TB5-2
A2 B2 S
02
A B
TB15
1 2
MA
L1
Leave the male
connector on
CN41 as it is.