- 27 -
[
II
Restrictions ]
Wiring method/address setting method
1) Indoor/outdoor transmission line
Same as [4] 1.
2) MA remote controller wiring
[When 2 remote controllers are connected to the system]
When two remote controllers are connected to the system, connect terminals 1 and 2 of the terminal block (TB15)
on the indoor unit (IC) to the terminal block on the MA remote controllers (option).
Set the Main/Sub switch on the connected MA remote controllers (option) to SUB.(See the installation manual for the
MA remote controller for the setting method.)
3) Switch setting
Address setting is required as follows.
Pro
ce-
du-
res
Unit or controller
Address-
settin-
grange
Setting method
Notes
Facto-
ry set-
ting
1
Indoor
unit
Main unit IC
01 to 50
Assign a sequential odd number
starting with "01" to the upper indoor
controller.
00
Sub unit
IC
01 to 50
Assign sequential numbers starting
with the address of the main unit in
the same group. (Main unit address
+1)
2
Outdoor unit
OC
51 to 100
Add 50 to the address assigned to
the indoor unit connected to the sys-
tem with one outdoor unit.
00
3
MA
remote
controller
Main
remote
controller
MA
No set-
tings re-
quired.
-
Main
Sub
remote
controller
MA
Sub
remote
controller
Settings to be made with the sub/
main switch
Summary of Contents for PU(H)Y-P250YGM-A
Page 9: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 41: ... 32 ...
Page 53: ... 44 ...
Page 67: ... 58 ...
Page 73: ... 64 ...
Page 81: ... 72 ...
Page 83: ... 74 ...
Page 105: ... 96 ...
Page 107: ... 98 ...
Page 117: ... 108 ...
Page 119: ... 110 ...
Page 183: ... 174 ...