- 153 -
[
IX
Troubleshooting ]
(2) Outdoor unit LEV
The valve opening changes according to the number of pulses.
<Connections between the outdoor unit MAIN board and LEV1 (outdoor unit expansion valve)>
Pulse signal output and valve operation
LEV valve closing and opening operation
LEV
DC 12V
Outdoor MAIN board
M
4
6
2
3
5
1
4
5
6
3
2
1
4
5
6
3
2
1
4
3
2
1
Red
Brown
Blue
Orange
Yellow
White
Drive circuit
1
2
3
4
5
6
7
8
1
ON OFF OFF OFF OFF OFF ON ON
2
ON ON ON OFF OFF OFF OFF OFF
3
OFF OFF ON ON ON OFF OFF OFF
4
OFF OFF OFF OFF ON ON ON OFF
Output pulses change in the following orders when the
Valve is closed; 1 2 3 4 5 6 7 8 1
Valve is open; 8 7 6 5 4 3 2 1 8
*1. When the LEV opening angle does not change,
all the output phases will be off.
*2. When the output is open phase or remains ON,
the motor cannot run smoothly, and rattles and vibrates.
Output
(phase)
number
Output state
*When the power is turned on, the valve closing signal of 520 pulses
will be output from the indoor board to LEV to fix the valve position.
It must be fixed at point A.
(Pulse signal is output for approximately 17 seconds.)
When the valve operates smoothly, there is no sound from the LEV and no
vibration occurs, but when the valve is locked, noise is generated.
*Whether a sound is generated or not can be determined by
holding a screwdriver against it, then placing your ear against the handle.
*If liquid refrigerant flows inside the LEV, the sound may become smaller.
B
A
Fully open: 480 pulses
Pulses
Valve opening (refrigerant flow rate)
Valve closed
Valve open
Summary of Contents for PU(H)Y-P250YGM-A
Page 9: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 41: ... 32 ...
Page 53: ... 44 ...
Page 67: ... 58 ...
Page 73: ... 64 ...
Page 81: ... 72 ...
Page 83: ... 74 ...
Page 105: ... 96 ...
Page 107: ... 98 ...
Page 117: ... 108 ...
Page 119: ... 110 ...
Page 183: ... 174 ...