- 107 -
[
VIII
Test Run Mode ]
[7] Standard Operation Data (Reference Data)
(1) Cooling operation
Operation
Indoor unit model
Outdoor unit model
PFD-P500VM-E PUHY-P500YGM-A
Operat-
ing condi-
tions
Ambient
tempera-
ture
Indoor
DB/
WB
°C
27/19
Outdoor
35/-
Piping
Total pipe length
m
7.5
Outdoor
unit
Compressor frequency
(No.1/No.2)
Hz
50Hz:70/50
60Hz:62/60
LEV
opening
Indoor unit
Pulse
593
SC (LEV1)
193
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
2.90/0.99
Temp. of
each sec-
tion
Outdoor
unit
Discharge
(TH11/TH12)
°C
84/85
Heat exchanger out-
let (TH5)
43
Compressor inlet
22/23
Compressor shell
bottom
43/45
SC heat exchanger
outlet (TH7)
26
Bypass outlet (TH8)
15
Indoor
unit
LEV inlet
26
Heat exchanger
outlet
18